3.0 GETTING STARTED
3-8
CyberCat 254/1016 Programming Manual
Rev 3, 08/2013
P/N: 06-539
3.4.3 HOW TO ADDRESS DEVICES WITH THE IR TOOL (P/N 55-051)
The IR tool is a hand-held remote control that is designed to communicate with the CyberCat addressable
devices via infrared signals. The tool gives you the ability to assign an address to a new device that is
connected to the panel’s signaling line circuit (SLC).
By default the IR communication is disabled on the CyberCat loops. The user must first enable the IR
communication to allow the tool the ability to communicate with the devices connected to the SLC. Enabling
the IR communication requires a Level 3 password (Distributor Level).
To turn on IR Communication:
1. Press the ESCAPE key until the CyberCat’s TOP LEVEL MENU is displayed.
2. Press the F6 key to display the IR COMMUNICATION screen (IR COMM).
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A I R C O M M U N I C A T I O N
B L O O P 1 : D I S
L O O P 2 : D I S
C L O O P 3 : D I S
L O O P 4 : D I S
D
Exhibit 3-12: IR Communication Screen
•
Rows B & C - Displays the IR Communication status by loop. Enable only one loop at a time. Use
the
◄►
keys to move the cursor to the field; then use the +/- keys to toggle the ENAble/DISable
status of the loop. Disable the IR when complete or Reset the control panel (turns IR back OFF).