4.0 CONFIGURATION MENU
CyberCat 254/1016 Programming Manual
4-49
P/N: 06-539
Rev 3, 08/2013
4.5.5.4 HOW TO SET FAN RESTART MODE
The Fan Restart screen allows you to select whether CRM4 relays configured for fan restart will activate
automatically upon reset or require a manual input for activation following a panel reset.
From the “Relay Configuration Menu” screen, press the F4 key to access the “Fan Restart” screen, as shown
below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
S E L E C T
F A N
R E S T A R T
B
M O D E :
A U T O M A T I C
C
D
Exhibit 4-75: Fan Restart Configuration Screen
•
Row B - This field allows you to select whether relays configured for Fan Restart automatically
transfer after set time or if the set time begins upon a manual input.
AUTOMATIC
(factory default) – Upon activation of an ALARM event, the CRM4 relays will activate
and remain active until panel is reset. Once the panel is reset, the fan restart sequence begins and
fan restart relays will deactivate according to their programmed time delay.
MANUAL
– Upon activation of an ALARM event, the CRM4 relays will activate and remain active
until panel is reset. After panel reset, the fan restart sequence is delayed until the operator activates
any of the following switch sources: 1) Panel’s ENTER key, 2) monitor module configured for Fan
Restart, 3) RDU switch configured for Fan Restart. Upon switch activation, the panel will initiate the
automatic fan restart sequence and the relays will deactivate according to their programmed time
delay. Once all relays are deactivated, the panel will return to normal operation.
4.6
CONFIGURATION MENU 5
From the “Configuration Menu 4” screen, press the F6 key to access the “Configuration Menu 5” screen, as
shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
C O N F I G U R A T I O N
M E N U
5
B
F 1 - L O G O
F 4 - D I A L E R
C
F 2 - A U T O
A
F 5 - N E T W O R K
D
F 3 -
F 6 - M E N U
6
Exhibit 4-76: Configuration Menu 5
F1
= Edit Panel Logo Screen
F2
= Auto Addressing Screen
F3
= Not Used
F4
= Dialer Auto Test Screen
F5
= Network Configuration Menu
F6
= Configuration Menu 6