4.0 CONFIGURATION MENU
4-10
CyberCat 254/1016 Programming Manual
Rev 3, 08/2013
P/N: 06-539
G. HOW TO SET THE AHU RELAY RE-START DELAY
Each addressable relay assigned to AHU shutdown, can be configured with a time delay that prevents the de-
activation of the relay until the set time delay expires. Time delay will begin only upon activation of an AHU
restart switch. This feature allows the startup of AHU’s to be staggered
From the “Alarm Features” screen, select the address of the relay assigned to AHU shutdown; then, press the
F3 key to access the “AHU Re-start Delay” screen, as shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
A H U R E L A Y
R E - S T A R T
B
D E L A Y : 0 3 3
S E C O N D S
C
D
Exhibit 4-14: Addressable Relay AHU Re-start Delay Screen
•
Row B - This field allows you to set a restart time delay (0 – 255 seconds). Use the
◄►
arrow keys
to position the cursor under the field; then use the +/- keys to increment or decrement the number
value.
Summary of Contents for CyberCat 10-064
Page 127: ......