4.0 CONFIGURATION MENU
CyberCat 254/1016 Programming Manual
4-7
P/N: 06-539
Rev 3, 08/2013
C. HOW TO MODIFY A MONITOR MODULE
The default programming options for a sample monitor module are shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
1 - 0 0 1 : M O N I T O R
M O D U L E
B
F U N C : * - - - - - - - - - - - - N O
C
C U S T O M
M E S S A G E
1 - 0 0 1
D
Z O N E : 0 0 0
0 0 0
0 0 0
0 0 0
Exhibit 4-10: Alarm Features Screen (Monitor Module)
•
Row A - Displays the loop and address of the selected SLC device.
•
Row B - This field allows you to select the input function for the selected device. To cycle through
the possible input functions, use the
◄►
arrow keys to position the cursor under the function field;
then use the +/- keys to change the function:
Pre-Alarm
I
Supervisory
AHU
Fire
Key
Pre-Alarm
2
Reset MNS
Message
Man
Alarm Silence
Voice
Messg
Waterflow Acknowledge
Voice
EVAC
Pre-Disch
1
Drill
Voice
Alert
Man Release
1
Zone Disable
Abort
1
PAS Inhibit
Process
Watermist
Trouble
Fan
Restart
Detection
Smoke
Control
Feedback
Man. Alarm 2
nd
Stage
•
Row B - The last two fields on this row allow you to select whether the module will be monitoring
Normally Open (NO) or Normally Closed (NC) contacts. Not all input functions provide the option of
NO/NC contacts as follows:
Pre-Alarm I
NO/NC
Supervisory
NO
AHU Fire Key
NO
Pre-Alarm 2
NO/NC
Reset
NO
MNS Message
NO
Man Alarm
NO
Silence
NO/NC
Voice Messg
NO
Waterflow NO Acknowledge
NO/NC
Voice
EVAC
NO
Pre-Disch
1
NO Drill
NO/NC
Voice
Alert
NO
Man Release
1
NO Zone
Disable
NO/NC
Abort
1
NO PAS
Inhibit
NO/NC
Process NO/NC
Watermist
NO
Trouble NO/NC
Fan
Restart
NO/NC
Detection NO Smoke
Control
NO
Man Alrm. 2
nd
NO
•
Row C - Displays the 20 character custom message for the selected address. Use the
◄►
arrow
keys to position the cursor under any of the fields; then use the +/- keys to cycle through all
available ASCII characters.
•
Row D - The 000 fields allow you to set zone settings for the selected device address in Row A.
Use the
◄►
arrow keys to position the cursor under one of the zone number fields (000); then use
the +/- keys to change the zone number. To add multiple zones, use the
◄►
arrow keys to move
the cursor to the 2nd-3rd zone number fields; then use the +/- keys to change or add the zone
number.
L
Note:
These programming options are typical for the mini and dual input monitor modules as well.
1
Available on Cheetah Xi panels only.