4.0 CONFIGURATION MENU
4-6
CyberCat 254/1016 Programming Manual
Rev 3, 08/2013
P/N: 06-539
MODULE FUNCTIONALITY - SELECT DEVICE
This function setting requires a state broadcast matching the activation state to come from the selected
device loop-address shown in Row A before the control modules output will activate.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
1 - 0 0 1 : C O N T R O L
M O D U L E
B
F U N C : * S E L E C T
D E V I C E
C
C U S T O M
M E S S A G E
1 - 0 0 1
D
L O O P : 0
A D R : 0 0 1
P : *
Exhibit 4-8: Select Device Function Screen
•
Row D -These fields allow you to select the loop and address of a specific SLC device that will
activate the selected control module. Use the
◄►
arrow keys to position the cursor under any of
the fields; then use the +/- keys to change to a different loop or address number.
P:X
allows you to select the activation pattern for the modules output, where X signifies:
0 = OFF F = FAST
1 = ON T = TEMPORAL
S = SLOW W = WALKTEST)
Use the
◄►
arrow keys to position the cursor under pattern field; then use the
+/-
keys to change
the activation pattern.
MODULE FUNCTIONALITY - ROW ANDING
This function setting requires all of the priority rows specified in Row D to become active before the control
modules output will activate.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
1 - 0 0 1 : C O N T R O L
M O D U L E
B
F U N C : * R O W
A N D I N G
C
C U S T O M
M E S S A G E
1 - 0 0 1
D
R : 0 0 0 0
0 0
0 0
P : *
Exhibit 4-9: Row Anding Function Screen
•
Row D - These fields allow you to select the priority rows that must be active before the output of the
selected control module activates. Use the
◄►
arrow keys to position the cursor under any of the
fields; then use the +/- keys to set the priority row.
P:X
allows you to select the activation pattern for the modules output, where X signifies:
0 = OFF F = FAST
1 = ON T = TEMPORAL
S = SLOW W = WALKTEST)
Use the
◄►
arrow keys to position the cursor under pattern field; then use the
+/-
keys to change
the activation pattern.