4.0 CONFIGURATION MENU
CyberCat 254/1016 Programming Manual
4-35
P/N: 06-539
Rev 3, 08/2013
4.4.1.2
HOW TO SET THE PERIPHERAL BUS COMMAND SOURCE
The “Peripheral Bus Command Source” screen is used to direct the communication path for configuration of
peripheral devices connected to the panel.
From the “Peripheral Menu” screen, press the F2 key to access the “Peripheral Bus Source” screen, as
shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
P E R I P H E R A L
B U S
B
C O M M A N D
S O U R C E :
C
P A N E L
D
Exhibit 4-53: Peripheral Source Screen
•
Row C - Use the +/- keys to toggle field value from Panel to USB Connector.
PANEL
mode is set by default and allows the panel to communicate with peripheral devices
connected to the CyberCat 254, CyberCat 1016 and Cheetah Xi panel’s RS485 bus. In this mode,
peripheral device configuration is transmitted during the panel configuration process via the panel’s
P5 Peripherals jack. You will be prompted by the C-Linx software to move the programming cable
from the P3 Computer jack to the P5 Peripherals jack to transmit the device configurations.
USB CONNECTOR
mode is used for CyberCat 50 and Cheetah Xi 50 peripheral device
configuration. In this mode, peripheral device configurations are transmitted during the panel
configuration process via the panel’s P3 PC/USB jack. You must keep the cable in the USB port,
enter the Level 3 password at the panel and go to this menu to re-direct the configuration information
out the peripheral bus.
L
Note:
After a system reset, the peripheral source will return to the default
PANEL
mode.
4.4.1.3
HOW TO SET THE PERIPHERAL BUS SPEED
The “Peripheral Bus Speed” screen is used to set the communication speed used by all peripheral devices
connected to the panel.
From the “Peripheral Menu” screen, press the F3 key to access the “Peripheral Bus Speed” screen, as shown
below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
B
P E R I P H E R A L
B U S
S P E E D
C
9 6 0 0 B P S
D
Exhibit 4-54: Peripheral Bus Speed Screen
•
Row C - Use the +/- keys to toggle field value from
9600 bps
(factory default) to
38400 bps
.
I
CAUTION
All devices connected to the peripheral bus must be capable of
supporting the higher 38400 bps communication speed if the
setting is to be used. Otherwise, 9600 bps must be used.