4.0 CONFIGURATION MENU
4-58
CyberCat 254/1016 Programming Manual
Rev 3, 08/2013
P/N: 06-539
4.7.3 HOW TO SET IP TIME PARAMETERS
The IP Time screen allows you to set additional parameters for how data is transmitted on the network. From
the Configuration Menu 6 screen, press the F3 key to access the IP Time screen, as shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
I P S U P E R V I S I O N
B
T I M E O U T :
0 4
M I N U T E S
C
H I S T O R Y
T R A N S M I T S : 0 1
D
I P T I M E :
D I S A B L E D
Exhibit 4-92: IP Time Screen
•
Row B - This field allows you to set how long the supervising panel will wait to annunciate a
“MISSING” trouble should the supervising panel lose communication with a supervised panel. Use
the
◄►
arrow keys to position the cursor under the field; then use the +/- keys to toggle to select
time.
This parameter can be configured in one of the following increments:
5-55 seconds, 5 second increments
1-59 minutes, 1 minute increments
1-18 hours, 1 hour increments
L
Note:
This parameter only applies when the respective panel is configured to supervise other
panels.
•
Row C - This field allows you to set how many times a single history event will be transmitted to the
peripheral bus. This setting greatly affects the reliability of the Ethernet reporting system. The value
can be configured from 1 to 10:
1 = Provides the greatest amount of speed but is the least reliable.
10 = Provides a reduction in speed but is the most reliable.
Use the
◄►
arrow keys to position the cursor under the field and use the
+/-
keys to
increment/decrement the field.
L
Note:
For Ethernet applications, Fike recommends a History Transmit setting of 2. Otherwise,
the default value of 1 is recommended.
•
Row D - This field allows you to set whether the date and time of networked panels will be
synchronized with the main panel (DISABLED, ACCEPT, SEND):
DISABLED = Turns panel date/time synchronization feature off. Each panel will use its own
date/time settings.
ACCEPT = Sets panel to accept date/time synchronization settings from sending panel.
SEND = Sets panel to transmit date/time synchronization settings to all network panels.