4.6.3 HOW TO CONFIGURE DIALER TEST
The Dialer screen allows you to configure the CyberCat panel to periodically perform an operational test of
the dialer. This test will send a contact ID code 50 (Auto Test) to the monitoring facility.
From the “Configuration Menu 5” screen, press the F4 key to access the “Dialer Configuration” screen, as
shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
D I A L E R
A U T O
T E S T
B
R E P E A T
C Y C L E : D I S A B L E
C
S T A R T I N G
H O U R : 0 2 A M
D
Exhibit 4-79: Dialer Configuration Screen
•
Row B - This field allows you to set the number of hours that must elapse before the second and
successive dialer tests are performed. Configurable options include ‘06Hours’, ‘12Hours’, and
‘24Hours’. Use the +/- keys to change the value at the cursor. Default is ‘DISABLE’ for no test.
•
Row C - This field allows you to set the starting hour to begin the daily dialer test. Configurable
between 0 and 23 hours, where the default is 2 AM. Use the
◄►
arrow keys to move cursor to the
field; then use the +/- keys to increment/decrement the time.
L
Note:
The Contact ID dialer is capable of performing its own operational tests. Configuring the
panel to initiate its own test might be redundant and could be considered a nuisance to the
monitoring company. Only utilize this feature if instructed to do so by the local authority.
4.6.4 HOW TO CONFIGURE PANEL NETWORK
The Network Configuration menu provides configuration options associated with the CyberCat’s P20 network
module.
From the “Configuration Menu 5” screen, press the F5 key to access the “Network Configuration Menu”
screen, as shown below:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
C O N F I G U R E
N E T W O R K
B
F 1 - I D ‘ S
F 4 - H I S T
T R
C
F 2 - M O D U L E
F 5 - S W I T C H
D
F 3 - Z O N E S
Exhibit 4-80: Network Configuration Menu
F1
= Configure panel’s network ID and supervision
F2
= Configure network module type and settings
F3
= Select zones this panel should participate in
F4
= Enable/Disable panel’s network operations
F5
= Configure how panel responds to switches