Festo — MSE6-E2M — 2022-08d
Functions
23
Data format of output word 16 bits, right-justified
B2
Pressurising
B12
Consumption measurement start/stop
B13
Consumption measurement reset
B3 … B11
Irrelevant data bits
B14, B15
Irrelevant data bits
D0 … D15
16-bit output data field
MSB/LSB
Most significant bit/least significant bit
Tab. 4: Data format of output word Am.0
Blocking function output data
Data bit B0 has the following values:
–
0 = open shut-off valve, pressurisation state - default
–
1 = close shut-off valve , blocking state
Data bit B1 has the following values:
–
0 = deactivation of the automatic blocking function, auto blocking, activation of the shut-off valve
via the output bit B0, default
–
1 = activation of the automatic blocking function, auto blocking
Data bit B2 has the following values:
–
0/1 = open shut-off valve, pressurisation state, on positive signal edge
–
0 = no change in status with static signal level, default
–
1 = no change in status with static signal level
Consumption measurement output data
Data bit B12 has the following values:
–
0 = consumption measurement inactive. Consumption measurement is stopped, default
–
1 = consumption measurement active. Consumption measurement is started or continued.
Data bit B13 has the following values:
–
0 = reset function, consumption measurement inactive, default
–
1 = reset function, consumption measurement active. The consumption measurement value is reset
to the value 0.
5.2.2.2
Input word Em.0 flow rate
In the input word Em.0, the flow rate value is displayed in accordance with the parameterised flow
rate unit and flow rate standard. The default value of the unit flow rate module parameter is l/min, the
default value of the flow rate standard module parameter is DIN 1343.
Data format of input word Sign + 15 bits, right-justified
D15
D14
D13 D12 D11 D10 D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
VZ
B14
B13 B12 B11 B10 B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB