Removal
Error
channel
Meaning
Remedy
Enable parameter
m = module
number 1
Error number 26, actuator power supply undervoltage;
Depending on the parameterisation, the module reports the error when monitoring is activated.
Input signals will, however, still be processed.
Am.0
Load voltage U
OUT/A
below the permitted
range
–
Check load voltage U
OUT/A
and
increase if necessary.
–
Check the wiring of the load voltage
supply and repair if required.
Monitoring: 4828 +
m * 64 + 0, Bit 2,
monitoring actuator
power supply under-
voltage
Error number 29, error in parameterisation;
Depending on the parameterisation, the module reports the error when monitoring is activated.
Input signals will, however, still be processed. The parameter values entered will be ignored. The
module operates internally with the last valid parameter values.
Em.0 …
Em.3
–
Monitor limit
values startup
–
Unit pressure
–
Unit flow rate
–
Unit Consumption
–
Flow standard
–
Pressure change
sample time
Channel-dependent
error distinction
–
Check parameterisation and parame-
terise again with correct parameters,
valid parameters
Monitoring: 4828 +
m * 64 + 0 (bit 7)
monitoring of param-
eter error
Tab. 63: Module-specific error numbers
11
Removal
The settings are not saved in the product. Save the settings if necessary, e.g. on the higher-level
controller.
Disassemble the product in the following sequence:
1. De-energise the compressed air supply and power supply.
2. Exhaust the energy efficiency module.
3. Disconnect the pneumatic ports.
4. Disconnect all electrical cables.
5. Loosen the screws from all mounting brackets, one after the other. Start with the screws beneath
the product.