Festo — MSE6-E2M — 2022-08d
Commissioning
51
LED displays on the bus node CPX-M-FB43 and CPX-M-FB44
1
2
Fig. 27: LED display on the bus node CPX-M-FB43
and CPX-M-FB44
1
Network-specific LEDs
2
CPX-specific LEDs
Network-specific LEDs
1)
CPX-specific LEDs
2)
NF
Network failure, red
PS
Power system, green
M/P
Maintenance/PROFlenergy, green
PL
For MSE6-E2M without function.
TP1
Link 1, green
SF
System failure, red
TP2
Link 2, green
M
Modify, yellow
3)
1) If there is no network connection, the NF LED flashes.
2) In the standard operating status all green LEDs are on. The yellow and red LEDs are not on.
3) Parameterisation modified or force active.
Tab. 35: LED displays
8.6.2
Using the memory card
The memory card is used as a carrier of configuration data for PROFINET addressing and thus simpli-
fies bus node replacement:
–
PROFINET I/O device name
–
IP address
NOTICE
Malfunction or Damage to the Memory Card.
Inserting or removing the memory card while the power supply is switched on can result in malfunc-
tions of or damage to the memory card.
• Disconnect the power supply before you insert or remove the memory card.
Data stored on the memory card has priority over other configuration data which is stored, e.g. in the
bus node memory or in the higher-order controller.
1. Switch off the power supply.
2. Unscrew the retaining screws of the cover.
3. Remove the cover.
4. Insert the memory card.