Malfunctions
Error
channel
Meaning
Remedy
Enable parameter
m = module
number 1
Error number 0, no error or end of a message status
–
–
–
Cannot be deacti-
vated
Error number 10, upper limit value exceeded;
Depending on the parameterisation, the module reports the error when monitoring is activated.
Input signals will, however, still be processed.
Em.0
Upper flow rate limit
value exceeded
–
Check flow.
–
Check parameterised limit value.
–
If necessary, adjust the diagnostics
limit values startup parameter.
Monitoring: 4828 +
m * 64 + 0, bit
6, monitoring limit
values
Upper pressure limit
value module param-
eter.
Em.2
Upper pressure limit
value exceeded
–
Check pressure.
–
Check parameterised limit value.
–
If necessary, adjust the diagnostics
limit values startup parameter.
Em.3
Upper pressure
change limit value
exceeded
–
Check pressure change.
–
Check parameterised limit value.
–
If necessary, adjust the diagnostics
limit values startup parameter.
–
Check system for leakage.
Error number 15, module/channel failed;
All electrical module functions are stopped.
Em.0
Flow sensor defec-
tive
–
Power off/on necessary.
–
If this error occurs again, replace
device.
Cannot be deacti-
vated
Em.2
Pressure sensor
defective
–
Check whether the input pressure is
too high.
–
Power off/on necessary.
–
If this error occurs again, replace
device.