2. Commissioning
2−33
Festo P.BE−CPX−FB23−EN en 0308NH
Address
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
20H + x
Station type:
0: Remote I/O
station
1: Remote device
station
2: Local station
or intelligent
device station
Stations:
1: Slave occupies
1station
2: Slave occupies
2 stations
3: ... 3 stations
4: ... 4 stations
CC−Link slave address:
1 .. 64 (01
H
... 40
H
)
x = CC−Link slave address
Tab.2/15:
Station data
Examples:
Memory address
Value
Meaning
20
H
.
.
1101
H
.
.
CC−Link slave address 1
1 station per slave
Remote device station
23
H
1205
H
CC−Link slave address 5
2 stations per slave
Remote device station
Tab.2/16:
Example of station data