1. Installation
1−22
Festo P.BE−CPX−FB23−EN en 0308NH
Branch lines
The following table shows the specification for branch lines
(without repeater) with the CC−Link reference cable.
Theme
Specification
Remarks
Baud rate
625 kBd
156 kBd
10 / 5 / 2.5 MBd not possible.
Maximum length of main
string
100 m
500 m
Cabel length between the terminating resistors
without the length of the branch line cables.
Max. branch line length
8 m
Total cable length for a branch line.
Max. total length of
branch lines
50 m
200 m
Total cable length for all branch lines.
Max. number of slaves
per branch line
6 slaves per branch
line
Total number of connectable slaves depends on
CC−Link specification.
Connecting cable
CC−Link reference
cable
CC−Link high−perfomance cable cannot be used
(e.g. FANC−SBH).
The use of different cables is not possible.
Branch line sub−bases
Commercially−avail
able branch line
sub−bases
Remove as little insulation as possible from the
cable when it is connected to the main string.
Branch line connectors
Recommended
connectors for FA
sensors:
NECA4202
(IEC947−5−2) or
compatible
Distance between
branch lines
As desired
Distance between branch lines
(branch line sub−bases or branch line connectors).
Length A
< 0.3 m
Cable length between remote I/Os or remote
device stations.
Length B
< 1 m
1)
< 2 m
2)
Cable length for master, local and intelligent device
stations as well as the adjoining stations.
1)
More than 1 m if only remote I/Os and remote device stations are available.
2)
More than 2 m if local or intelligent device stations are available.
Tab.1/12:
Specification for branch lines
Summary of Contents for CPX-FB23
Page 2: ......
Page 4: ...Contents and general instructions II Festo P BE CPX FB23 EN en 0308NH...
Page 15: ...Installation 1 1 Festo P BE CPX FB23 EN en 0308NH Chapter 1...
Page 45: ...Commissioning 2 1 Festo P BE CPX FB23 EN en 0308NH Chapter 2...
Page 86: ...2 Commissioning 2 42 Festo P BE CPX FB23 EN en 0308NH...
Page 87: ...Diagnosis and error treatment 3 1 Festo P BE CPX FB23 EN en 0308NH Chapter 3...
Page 104: ...3 Diagnosis and error treatment 3 18 Festo P BE CPX FB23 EN en 0308NH...
Page 105: ...Technical appendix A 1 Festo P BE CPX FB23 EN en 0308NH Appendix A...
Page 117: ...Index B 1 Festo P BE CPX FB23 EN en 0308NH Appendix B...
Page 118: ...B Index B 2 Festo P BE CPX FB23 EN en 0308NH Contents B Index B 1 B 1 Index B 3...