1. Installation
1−21
Festo P.BE−CPX−FB23−EN en 0308NH
1.3.2
Field bus baud rate and field bus length
The maximum permitted field bus length depends on the
baud rate used. The following table shows the baud rates
which can be used (CC−Link version 1.10 compatible refer
ence cable, terminating resistor 110 ).
Baud rate
Cable length between stations
Max. total cable length
156 kBd
1200 m
625 kBd
600 m
2.5 MBd
> 0.2 m (for all baud rates)
200 m
5 MBd
150 m
10 MBd
100 m
Master
station
Remote I/O station/
Remote device
station
1)
Local station/
intelligent device
station
Local station/
intelligent device
station
Cable length
between stations
Total cable length
Remote I/O station/
Remote device
station
1)
1)
CPX terminal with field bus node CPX−FB23 = remote device station
Tab.1/11:
Baud rate and field bus length
Summary of Contents for CPX-FB23
Page 2: ......
Page 4: ...Contents and general instructions II Festo P BE CPX FB23 EN en 0308NH...
Page 15: ...Installation 1 1 Festo P BE CPX FB23 EN en 0308NH Chapter 1...
Page 45: ...Commissioning 2 1 Festo P BE CPX FB23 EN en 0308NH Chapter 2...
Page 86: ...2 Commissioning 2 42 Festo P BE CPX FB23 EN en 0308NH...
Page 87: ...Diagnosis and error treatment 3 1 Festo P BE CPX FB23 EN en 0308NH Chapter 3...
Page 104: ...3 Diagnosis and error treatment 3 18 Festo P BE CPX FB23 EN en 0308NH...
Page 105: ...Technical appendix A 1 Festo P BE CPX FB23 EN en 0308NH Appendix A...
Page 117: ...Index B 1 Festo P BE CPX FB23 EN en 0308NH Appendix B...
Page 118: ...B Index B 2 Festo P BE CPX FB23 EN en 0308NH Contents B Index B 1 B 1 Index B 3...