4. Commissioning
4-7
Festo P.BE-VIFB13-03-EN en 0003c
Basic rules of addressing
With mixed fitting, the address assignment of the valves, digi-
tal I/O modules and status bits is taken into account.
Outputs
1. The address assignment of the outputs does not depend
on the inputs.
2. Address assignment of the valves:
– Assign the addresses in ascending order without gaps.
– Counting begins on the node from
left to right
.
– Maximum 26 valve solenoid coils can be addressed.
Type 03:
– Single-solenoid sub-bases always occupy 2 addresses
– Double-solenoid sub-bases always occupy
4 addresses
Type 04-B
– Single-solenoid sub-bases always occupy 1 address
– Double-solenoid sub-bases always occupy
2 addresses
3. Round up to 4 bits: The following distinction is made:
a) If the number of valve addresses can be divided by 4
without remainder, continue with point 4.
b) If the number of valve addresses cannot be divided by 4
without remainder, you must round up to 4 bits because
of the 4-bit orientated addressing. The bits thus
rounded up in the address range cannot be used.
Summary of Contents for 174335
Page 2: ......
Page 4: ...Contents and general instructions II Festo P BE VIFB13 03 EN en 0003c...
Page 17: ...Summary of components 1 1 Festo P BE VIFB13 03 EN en 0003c Chapter 1...
Page 26: ...1 Summary of components 1 10 Festo P BE VIFB13 03 EN en 0003c...
Page 27: ...Fitting 2 1 Festo P BE VIFB13 03 EN en 0003c Chapter 2...
Page 37: ...Installation 3 1 Festo P BE VIFB13 03 EN en 0003c Chapter 3...
Page 66: ...3 Installation 3 30 Festo P BE VIFB13 03 EN en 0003c...
Page 67: ...Commissioning 4 1 Festo P BE VIFB13 03 EN en 0003c Chapter 4...
Page 123: ...Diagnosis and error treatment 5 1 Festo P BE VIFB13 03 EN en 0003c Chapter 5...
Page 162: ...5 Diagnosis and error treatment 5 40 Festo P BE VIFB13 03 EN en 0003c...
Page 163: ...Technical appendix A 1 Festo P BE VIFB13 03 EN en 0003c Appendix A...
Page 177: ...Index B 1 Festo P BE VIFB13 03 EN en 0003c Appendix B...
Page 178: ...B Index B 2 Festo P BE VIFB13 03 EN en 0003c...