A. Technical appendix
A-7
Festo P.BE-VIFB13-03-EN en 0003c
Calculating with the graph
Proceed as follows:
1. Calculate the maximum current consumption of the out-
puts/valves (I
2
).
2. Calculate the lowest voltage to be expected during oper-
ation (VB
min
) on thepower unit. When doing this, please
note:
– the load dependency of the power unit
– the fluctuations in the primary mains voltage
3. Read off the permitted cable length for your cross-
sectional area in the relevant table.
Example for 1.5 mm
2
:
V
Bmin
= 22.8 V, I
2
= 2 A; L
max
= 25 m
Summary of Contents for 174335
Page 2: ......
Page 4: ...Contents and general instructions II Festo P BE VIFB13 03 EN en 0003c...
Page 17: ...Summary of components 1 1 Festo P BE VIFB13 03 EN en 0003c Chapter 1...
Page 26: ...1 Summary of components 1 10 Festo P BE VIFB13 03 EN en 0003c...
Page 27: ...Fitting 2 1 Festo P BE VIFB13 03 EN en 0003c Chapter 2...
Page 37: ...Installation 3 1 Festo P BE VIFB13 03 EN en 0003c Chapter 3...
Page 66: ...3 Installation 3 30 Festo P BE VIFB13 03 EN en 0003c...
Page 67: ...Commissioning 4 1 Festo P BE VIFB13 03 EN en 0003c Chapter 4...
Page 123: ...Diagnosis and error treatment 5 1 Festo P BE VIFB13 03 EN en 0003c Chapter 5...
Page 162: ...5 Diagnosis and error treatment 5 40 Festo P BE VIFB13 03 EN en 0003c...
Page 163: ...Technical appendix A 1 Festo P BE VIFB13 03 EN en 0003c Appendix A...
Page 177: ...Index B 1 Festo P BE VIFB13 03 EN en 0003c Appendix B...
Page 178: ...B Index B 2 Festo P BE VIFB13 03 EN en 0003c...