Activate Warning
: Usually the
inlet warnings are disabled.
Limit Warning
: A ppm value at
which a water warning gets
triggered.
On Delay Warning
: The Inlet
water contamination must be
above the limit for the specified
time. Then a warning comes.
The warning relay gets
released and the blue lamp
blinks slowly.
Multiple Warnings cause
alarm
: Please activate this
setting if you want to have the
alarm relay released if there
occurred more than one
warning.
No. of Warnings to Fuel
Stop
:
The count of warnings which
must occur until the alarm relay
gets released and the blue
lamp blinks fast. This usually
should happen after the
second warning.
Sheet 3 of 4 (skipped if not available)
Activate Alarms
: If you want
to have a water alarm at
specified value (usually inlet
50ppm, outlet 30ppm)
Limit Alarms
: The limit at
which an alarm gets triggered
and the alarm relay gets
released.
On Delay Alarm
: The time the
water contamination must be
above the specified value until
the alarm relay gets triggered
and the blue lamp blinks fast.
Sheet 4 of 4 this page is skipped for both AFGUARD®
because water slug detection is always enabled for both
AFGUARD®s.
One Warning will release the warn relay (slow blinking LED)
Multiple warnings or one alarm or one water slug will release the alarm relay (fast blinking
LED).
This only will happen when the Water Monitoring is activated.