In case of the Signal type the screen will change:
Signal: Pulse
Signal: 0..20mA or 4..20mA
Fuel per Pulse:
For change click the blue box.
You were asked to enter the amount of fuel
which flowed through the pipe when the
sensor gave out one Pulse.
Enter a value and press Enter
↲
.
In this case it is 1.0 Liter per Pulse.
Max. Flow Range (20mA):
For change click the blue box.
You were asked to type in the flow, which is
represented by a sensor current of 20mA.
Enter a value and press Enter
↲
.
In this case it is 10000 Liters per Minute at
20mA.
You will come back to the Screen
You will come back to the Screen
Signal Attenuation time:
For attenuating the input signal, you can in insert a value of a
few seconds here. It is the time it will need until the step response of the input signal will
reach 63% of the end value. For a pulsed flow it is highly recommended not to use 0 sec
because the flow will have high peaks and will drop to zero if no pulses are coming. We
recommend a time of
2 sec or more
for a pulsed flow signal. Since firmware 2020-10-28
the attenuation time cannot be edit by admin password to simplify configuration
If max values do not fit your needs, please contact FAUDI Aviation GmbH to adapt for
your process.
Click Next >>