3.2.4.3.11 Datalogger
The following sheet will open.
The logging cycle is set to 2 Seconds and cannot be edit.
Please have in mind that only logged data could be analysed retroactive. Amount of data
increases linear with number of logs.
The logging of a refuelling process and the corresponding calculation for the refuelling history
can be started and stopped by the following options depending whether you connect an
interlock signal to the CCS Silver or not.
We recommend you connect an interlock signal to the system. The interlock signal will tell
the system when a refuelling process starts and when it ends. Also, it is possible to use the
CCS without an interlock signal. The differences will be explained in the following Table. As
“refuelling process” we call the whole time when the refuelling truck stands under an aircraft
and is ready to refuel or is actually refuelling.
Interlock Signal available:
Interlock Signal not available:
If you want to connect a binary interlock
signal to the system, then make sure the
box is checked
If you don’t connect an interlock signal to
the system, then uncheck the box.
A hysteresis for the interlock can be
configured. You can set the on and off delay
by a click on the blue boxes. If you are not
sure, we recommend, not to modify the two
values.
Since firmware 2020-10-28 the default
value for the follow-up-time is preset to 0
sec and cannot be edit.
If a failure of detection happens here it does
not affect on the safety, but the analysis of
the refuelling processes could be wrong.
E.g. the system logs the refuelling of two
aircrafts in one log file or it divides one
refuelling process into two log files.