The refuelling process will be during a high
of the interlock signal (regarding the set
hysteresis).
The refuelling process starts automatically
with the first activation of the monitoring by
the trigger, flow or differential pressure. It
ends the specified time after the trigger has
released
and
the flow
and
the DP are
below the set limits in the
Monitoring
chapter,
when you do not modify the
defaults, the refulling process ends with the
water monitoring simultanuosly.
The datalogger will log during the hole
refuelling process. It creates one logfile with
date and time of begin for each refuelling
process.
The Datalogger will also log during the hole
refuelling process, this means it creates
one file when the monitoring starts and
continue this file until the follow-up time
after the monitoring ends is over.
The history gets one record for the refuelling
process
The history gets one record for the
refuelling. This means also one record
which starts with the first monitoring in the
refuelling process and it ends after the set
follow-up time after the last monitoring is
over.
Ignore missing USB Drive / Battery Error:
Since firmware 2020-01-12 the CCS silver
generates an error when no USB drive is plugged in, or USB drive is faulty. As well there will
be an alarm generated when the battery is low and the date and time have invalid values. In
both cases the blue flashlight will stay off and the alarm relay gets released. If the lower
Ignore box is checked, no error will be generated and the alarm relay stays unaffected of
these cases.
Click Next >> to continue.
3.2.4.3.12 Finished
The following screen appears.
If you like to do some additional settings, which are not part of the installer, like
-
Signal Outputs
-
Modbus settings
-
Network settings
-
…
you can click Setup to go through the configuration menu.