The following page is for setting up the Pressure Sensor.
You are asked to select:
Signal:
•
N/A
•
0..20 mA
•
4..20 mA
For a change click on the < > Button.
You can use the CCS without a pressure sensor. If no pressure sensor is available, please
select N/A. The CCS supports an analog current driven differential pressure sensor with
ranges of 0..20mA and 4..20mA.
Max. Pressure Range (20mA):
Click on the blue box to change the value of the pressure
range. An input dialog will open and ask for a value. Please insert the value given by the
documentation of your differential pressure sensor.
Signal Attenuation time:
For attenuating the input signal, you can in insert a value of a few
seconds here. It is the time it will need until the step response of the input signal will reach
63% of the end value. We recommend a time of 2 sec or more for the signal of differential
pressure. Since firmware 2020-10-28 the attenuation time cannot be edit by admin password
to simplify configuration
Click Next >>