Troubleshooting
Issue
Reason
Solution
I cannot reach the web
visualisation with my
computer or smartphone
The system has not
been booted yet
Wait until the CCS has been booted. The
Status LED must light green permanently.
This can take up to 2 minutes
The PC or Smartphone
is not in the same
network with the CCS
Make sure the devices are connected,
directly with an Ethernet cable or via a
Wi-Fi router in between.
Make sure the PC, or smartphone has a
valid IP address.
If you connect directly to the CCS with an
Ethernet cable, make sure the network
adapter of the PC has a static IP
Address, no use of DHCP. Maybe a
restart of the PC is necessary after
change.
Apply a ping command to the IP address
of the CCS to check the connectivity.
The browser is too old
and does not support
HTML5
Get the latest version of your web
browser.
The URL of the web
visualisation is
miswritten
The URL is:
http://192.168.10.231:8080/webvisu.htm
Only if the IP Address o
f the CCS didn’t
get changed since delivery in factory
condition. Otherwise, replace the IP
address in the shown URL
The status LED of the
CCS is blinking. The
CCS does not boot.
There is a failure of the
device. Usually this
should not happen.
Note the blinking pattern and contact the
manufacturer.
The CCS shows wrong
values for analog
sensors.
Wrong signal type is
set
Do not mix up ranges 0..20mA and
4..20mA. go To Setup -> Sensor Input
and fix it.
Wrong signal limits are
set (Value for 20mA)
To Setup -> Sensor Input and fix it.
Refer to the datasheet of your sensor
The alarm relay is still
released.
The system has not
booted yet
Wait until the CCS has been booted.
There is an alarm in
memory.
Open the web visualisation (Dashboard)
to find the reason for the alarm.
The blue indicator lamp
is permanently off.
The system has not
booted yet
Wait until the CCS has been booted.
Interlock signal is
installed but it is 0V
Check wiring. check source of interlock
signal. If there is no interlock signal, go to
Setup -> Interlock and check settings.
Lamp or wiring is
broken
Check functionality of lamp
No USB drive plugged
Plug USB drive for datalogger or disable
check in “Datalogger” section
Date and time invalid
See “Wrong date and time”