Operating instructions 

CCS Silver 

Firmware 2021-01-14 

 

Page:

 57 

of:

 72 

 

FAUDI Aviation GmbH, Scharnhorststraße 7 B, D-35260 Stadtallendorf 

Manual_CCS_silver_Eng_
operation_version6.docx 

 

 

 
This means: 

When Water Monitoring is active at the moment: 

o

  No Water warnings Inlet/Outlet 

o

  No Water alarm Inlet/Outlet 

o

  No Water slug Inlet/Outlet 

No SLUGGUARD alarm 

No wire breaks (

𝐼 < 3.6𝑚𝐴

) or sensor errors (

𝐼 < 4𝑚𝐴

) on 

all expected

 sensors 

No Overflow 

No Over DP  

If the listed conditions don’t match, the reset won’t be accepted, affecting to the state of the 
relays and depending on the reason of the alarm to the blue flashlight 
 

 

Summary of Contents for CCS silver

Page 1: ...lendorf Manual_CCS_silver_Eng_ operation_version6 docx Contamination Control System silver CCS silver Filtration manager for guarding water contamination in aviation fuel by one or two AFGUARD free water sensors in refuelling applications guarding of additional information like flow or differential pressure with integrated data logger ...

Page 2: ...ck 10 2 6 Trigger 11 2 7 Reset 11 2 8 Water Indicator 11 2 9 Relay Outputs 11 2 10 Power Supply 11 2 11 Optional Output Signals 12 Digital Outputs 12 Relay Outputs 12 Analog Outputs 4 20mA 12 3 Operation 13 3 1 Connection Settings 13 3 1 1 Direct connection via Ethernet Cable 13 3 1 2 Connection via Wi Fi 14 3 2 Web visualisation 20 3 2 1 Structure 20 3 2 2 First Start Welcome screen 21 3 2 3 Impo...

Page 3: ..._ operation_version6 docx 3 2 6 5 Info screen 59 3 2 6 6 Software Override 61 3 2 6 7 Hardware Override 61 3 2 7 Datalogger 62 3 2 7 1 History 62 3 2 7 2 Logging 63 3 2 7 3 Note 63 3 3 Update via USB 64 4 List of settings 65 4 1 Basic Settings installer 65 4 2 Additional Settings not included in installer 67 5 Operational States 68 6 Troubleshooting 70 7 Index 72 ...

Page 4: ...red to previous firmware 2019 08 28 1 See Chapter 4 6 2021 01 14 Added features Modbus Support Optional Signal Output Ready Relay Hardware Override DI3 Import Export of configuration Simplification of Setup Installer FTP access for download of logfiles history AFGUARD optional Alarms USB drive detection low battery invalid date detection Changes Different default and recommended values Bugfixes Pl...

Page 5: ...ype plate to ensure that the equipment is connected to the correct mains voltage Protect against touching dangerously high electrical voltages Before opening the equipment it must be switched off and hold no voltages This also applies to any external control circuits that are connected The equipment is only to be used within the permitted temperature and operation ranges Check that the location is...

Page 6: ...ts may only be rectified by authorised and specially trained personnel If faults cannot be rectified the products must be taken out of service and secured against unintentional commissioning Repairs not described in these Operating Instructions may only be carried out by manufacturer or by a designated service organisation 1 5 Operational safety The CCS has been designed and tested according to th...

Page 7: ...ower supply when all other connections are made Please use proper tools for making the connections Use flexible copper wire to connect signals to the CCS We recommend flexible wire with a cross section of 1 mm It is not recommended to mount wires without ferrules An appropriate crimping tool must be used to apply the ferrules to the wires The wiring diagram is shown in the photography DO1 BLUE LED...

Page 8: ...L OUTPUT DO4 Optional Output free programmable 24V REL_1 REL_1 ALARM Relay REL_2 REL_2 WARN Relay REL_3 REL_3 Optional Output free programmable Default Ready REL_4 REL_4 Optional Output free programmable ANALOG OUTPUT AO1 Unused ANALOG OUTPUT AO2 Unused ANALOG OUTPUT AO3 Optional Output free programmable 4 20mA ANALOG OUTPUT AO4 Optional Output free programmable 4 20mA Please connect all signals a...

Page 9: ...e the DP as a trigger for the monitoring It also logs the DP The CCS can work with analog DP transmitters with a current range between 0 20mA and 4 20mA The ANALOG_3 terminal is for connecting a DP signal The mA Terminal is the path where the given current flows in For Ex i Safety a barrier is needed The barrier connects between DP sensor and CCS ANALOG_3 input To power and ground the barrier or t...

Page 10: ...nector of the terminal The Voltage Level of the Pulses must be between 12V and 24 The Pulse Input has an optional 10kΩ Pull Up Resistor which can be activated by the slide switch This will connect the PULSE Input via the Pull Up Resistor to 24V Use Only for flowmeter output with low active pulses NPN 2 4 SLUGGUARD A SLUGGUARD is a binary sensor which indicates water slug in pipes or vessels The SL...

Page 11: ...y a key switch In the CONTROL terminal panel there is a connector called RESET connect the reset switch to 24V and RESET that the current path gets closed when applying reset 2 8 Water Indicator To indicate water warnings and water alarms to the operator a blue flashlight should be connected to the CCS The 24V Light must be connected between the DO1 of the DIGITAL_OUTPUT terminal panel and GND 2 9...

Page 12: ...Eng_ operation_version6 docx 2 11 Optional Output Signals The following Output Signals are free programmable in the web visualisation This could be useful for mirroring the signal of the AFGUARD to an external PLC Go to Setup Signal Output in the web visualisation Digital Outputs DO2 DO3 DO4 Relay Outputs REL_3 Default Ready REL_4 Analog Outputs 4 20mA AO3 AO4 ...

Page 13: ...e IPv4 Network For connecting a Smartphone or Tablet PC a Wi Fi access point is required For an easy connection with a computer you only need an Ethernet cable Cat 5 or better 3 1 1 Direct connection via Ethernet Cable If you want to connect the computer directly without using a router with DHCP Server follow these instructions 1 Take your computer laptop 2 Open the settings of your Ethernet conne...

Page 14: ... automatic DHCP referring to the pictures 5 Open the configuration of your router by entering its IP address to your web browser It is printed to the device 6 Change access password to router configuration and note 7 Set the IPv4 Address of the router to from default to 192 168 10 1 8 Set the Subnet mask to 255 255 255 0 or set the Prefix length to 24 depending on the setup of your router 9 Your r...

Page 15: ...Version 6 Operating instructions CCS Silver Firmware 2021 01 14 Page 15 of 72 FAUDI Aviation GmbH Scharnhorststraße 7 B D 35260 Stadtallendorf Manual_CCS_silver_Eng_ operation_version6 docx ...

Page 16: ...Version 6 Operating instructions CCS Silver Firmware 2021 01 14 Page 16 of 72 FAUDI Aviation GmbH Scharnhorststraße 7 B D 35260 Stadtallendorf Manual_CCS_silver_Eng_ operation_version6 docx ...

Page 17: ...ver Firmware 2021 01 14 Page 17 of 72 FAUDI Aviation GmbH Scharnhorststraße 7 B D 35260 Stadtallendorf Manual_CCS_silver_Eng_ operation_version6 docx Now the address of the router changed from 192 168 1 1 to 192 168 10 1 You need to reconnect ...

Page 18: ...Version 6 Operating instructions CCS Silver Firmware 2021 01 14 Page 18 of 72 FAUDI Aviation GmbH Scharnhorststraße 7 B D 35260 Stadtallendorf Manual_CCS_silver_Eng_ operation_version6 docx ...

Page 19: ...Version 6 Operating instructions CCS Silver Firmware 2021 01 14 Page 19 of 72 FAUDI Aviation GmbH Scharnhorststraße 7 B D 35260 Stadtallendorf Manual_CCS_silver_Eng_ operation_version6 docx ...

Page 20: ...the CCS is powered on and wait about a minute until it has been booted The status LED on the CCS on the left side of the battery must stop blinking and stationary light green Start web browser The browser must support HTML5 Type in http 192 168 10 231 8080 webvisu htm Following dashboard screen should appear On first run the installer appears instead of the dashboard If there is a loading logo try...

Page 21: ...ware 2021 01 14 Page 21 of 72 FAUDI Aviation GmbH Scharnhorststraße 7 B D 35260 Stadtallendorf Manual_CCS_silver_Eng_ operation_version6 docx 3 2 2 First Start Welcome screen When you boot the CCS Silver the first time the welcome screen will appear ...

Page 22: ... the USB drive and plug it into the CCS again Move File to USB drive via File Transfer Protocol For the second option make sure your computer is connected to CCS via Local Area Network Start Windows Explorer or another FTP Client like FileZilla and enter ftp 192 168 10 231 c into the path field Make a subfolder config and drop the backup file CCS_Silver_config dat into this folder The full path sh...

Page 23: ...gh all necessary settings of the CCS On the first launch of the CCS the installer starts automatically with the language page It is highly recommended to use the installer to setup the CCS on installation instead of setting up every menu point individually Please go through the Installer meticulously and know what values you set up on every page There is a List of Settings at the end of the docume...

Page 24: ...4 3 1 Date and Time settings First menu is Date and Time Click on change button of Day Month Year Hour or Minute or press the zero button to Set the Second section to set the Seconds to 00 If you press a change button you will enter the appropriate menu This looks like the following For Setting the year please only type in the last two digits e g 19 for 2019 The latest date supported by the system...

Page 25: ...horststraße 7 B D 35260 Stadtallendorf Manual_CCS_silver_Eng_ operation_version6 docx Following PIN numbers are preconfigured Administrator PIN level 12345678 User PIN level 00000000 Make sure to remember changed PIN numbers In cases of loss of changed PIN numbers only FAUDI Aviation GmbH can reconfigure ...

Page 26: ...u The PIN must have 4 to 10 digits If you have entered a valid PIN you will go back to the following screen Changes affect immediately Please check the new PIN on the following screen Please repeat the same procedure to change the USER PIN level 3 2 4 3 3 Units change units Choose Next button to enter next menu step Units where you are asked to define measuring units for pressure and Volume To swi...

Page 27: ...ressure units You can choose between bar psi or kPa and fuel volume units between Liter l US gallon gal or Cube meter m If you change the Volume unit the Flow unit changes automatically It will be Liter per minute l min US gallon per minute gal min or Cube meter per hour m h Choose Next button to enter next menu step where you are asked to select the specific type of Pressure Sensor in use ...

Page 28: ...w Rate Sensor menu to set up flow sensor You are asked to select Signal N A Pulse most common type 0 20 mA 4 20 mA For a change click on the Button If you use an analog sensor it is very important not to mix up the ranges 0 20mA and 4 20mA Otherwise the system will work with invalid flow values or system will detect a sensor error or a wire break Please refer to original documentation of sensors t...

Page 29: ... current of 20mA Enter a value and press Enter In this case it is 10000 Liters per Minute at 20mA You will come back to the Screen You will come back to the Screen Signal Attenuation time For attenuating the input signal you can in insert a value of a few seconds here It is the time it will need until the step response of the input signal will reach 63 of the end value For a pulsed flow it is high...

Page 30: ...ential pressure sensor with ranges of 0 20mA and 4 20mA Max Pressure Range 20mA Click on the blue box to change the value of the pressure range An input dialog will open and ask for a value Please insert the value given by the documentation of your differential pressure sensor Signal Attenuation time For attenuating the input signal you can in insert a value of a few seconds here It is the time it...

Page 31: ...water crossing the optical path of AFGUARD give out average amount of free water as mathematical result coming from flow and free water measurement to give out averaged free water signal give out ALARM in case of high levels of water water slug If you do not know about calibration range of AFGUARD free water sensor please contact your FAUDI Aviation sales contact You need to have the serial no of ...

Page 32: ...sure range please adjust AFGUARD calibration range most of them should be calibrated for 0 to 50 ppm Signal Attenuation time For attenuating the signal you can enter a time The AFGUARD has already an internal attenuation but for a better water analysis we recommend a time of 1 second Since firmware 2020 10 28 neither the Measure range nor the attenuation time can be edit by admin password to simpl...

Page 33: ...ings to Fuel Stop The count of warnings which must occur until the alarm relay gets released and the blue lamp blinks fast This usually should happen after the second warning Sheet 3 of 4 skipped if not available Activate Alarms If you want to have a water alarm at specified value usually inlet 50ppm outlet 30ppm Limit Alarms The limit at which an alarm gets triggered and the alarm relay gets rele...

Page 34: ...ersion6 docx By a click on Next the following sheet will appear 3 2 4 3 6 2 AFGUARD Outlet Setting up the AFGUARD Outlet is the same procedure as setting up the AGUARD Inlet There are also 3 sheets 2 of them optional if AFGUARD Outlet is Available Please refer to the steps in the last chapter You can configure the AFGUARD Outlet with different parameters than the AFGUARD Inlet ...

Page 35: ...se the system with a SLUGGUARD then make sure the available box is checked Otherwise uncheck the box For fail safety the Inverted logic is used and cannot be edited This means that the system recognizes a water slug when there is a low level at the SLUGGUARD Input For realizing a hysteresis the system has an on and off delay of a few seconds for triggering an alarm This is preset to 5 and 1 sec an...

Page 36: ...types of Flow Meter and Differential Pressure sensor were set to N A 3 2 4 3 9 1 Rated Flow This input box disappears if no Flowmeter is installed Flow Rate Sensor type N A Please input the rated flow of your filter vessel or enter the max achievable max necessary Flow of your refuelling process here The effect of this value is to release the alarm relay immediately when the flow is higher than th...

Page 37: ...ible to use the CCS without an interlock signal The differences will be explained in the following Table As refuelling process we call the whole time when the refuelling truck stands under an aircraft and is ready to refuel or is actually refuelling Interlock Signal available Interlock Signal not available If you want to connect a binary interlock signal to the system then make sure the box is che...

Page 38: ...en the monitoring starts and continue this file until the follow up time after the monitoring ends is over The history gets one record for the refuelling process The history gets one record for the refuelling This means also one record which starts with the first monitoring in the refuelling process and it ends after the set follow up time after the last monitoring is over Ignore missing USB Drive...

Page 39: ...e Button to get to the dashboard or click 2x Back to get to the setup 3 2 4 3 14Check for the right settings If your sensors are connected wrong then the dashboard may show you some errors E g if no sensors are connected yet the screen could look like the following Make sure every sensor is connected properly If you don t connect a sensor which is expected by the system you will see Broken Wire Er...

Page 40: ... The Administrator has the following rights Change language Change system settings o Date and time o Display Units o User PIN and Administrator PIN o Datalogger settings o Network settings o Filter Parameter o Modbus Change sensor inputs o Flow Rate o Pressure o Interlock o SLUGGUARD o AFGUARD Inlet o AFGUARD Outlet Change Signal Outputs o Analog Output o Digital Output o Relay Output Config Backu...

Page 41: ... asked to enter your PIN number Use the buttons on the right side or your keyboard to type in the PIN Press Enter when you are finished Following PIN numbers are preconfigured Administrator PIN level 12345678 User PIN level 00000000 After entering your PIN number you should enter one of the following menu levels Admin Level User Level In User Setup you are only allowed to change language and date ...

Page 42: ...p is explained 3 2 5 1 Language For setting up the language click on the Language Button Menu will open Please select language and click back 3 2 5 2 System By a click on System the following submenu gets opened The settings for Display Units Date and Time Change PIN Datalogger Filter Parameter Are the same as in the installer Click on the corresponding button for changes The sub menu will open By...

Page 43: ...uld be in range 192 168 10 24 The internet gateway is the address of the router which connect the subnet with the internet To change the IP Address Subnet mask or Internet gateway click on the corresponding blue box A dialog will open Use the keypad on the right to type in the decimal IPv4 address in four octets separated by a dot and press Enter You will go back to the last screen It is very impo...

Page 44: ...inistrator PIN If you need to modify water monitoring settings please contact FAUDI Aviation 3 2 5 2 3 Modbus If you click on Modbus the following screen appears you can change the Modbus RTU Slave address here For more information about the CCS Silver Modbus TCP RTU interface refer to the CCS Silver Modbus Application Note 3 2 5 3 Sensor Input By a click on Sensor Input the submenu gets opened If...

Page 45: ...For the meaning of every menu point please refer to the installer The menu structure is Sensor Input o Flow Rate Signal Type N A Pulse 0 20mA 4 20mA Fuel per Pulse or Max Flow Range 20mA Signal Attenuation time o Pressure Signal Type N A 0 20mA 4 20mA Max Pressure Range 20mA Signal Attenuation time o SLUGGUARD Available Not available Invert Signal On Delay Off Delay o AFGUARD Inlet Signal Settings...

Page 46: ...s opened Click on one of the three buttons to open the submenu 3 2 5 4 1 Analog Output The output channels AO_3 and AO_4 are configured to give out a 4 20mA Signal Click on the button to change the functionality You can give out following signals if connected otherwise they were skipped AFGUARD Inlet AFGUARD Outlet Flow DP If you use a pulsed flowmeter and want to give out the flow signal the syst...

Page 47: ...lay is specified minimum fuel minimum time 4 Refuelling active Logging If no interlock is activated in setup the logging begins with Monitoring and ends after off delay of monitoring 5 SLUGGUARD Water Slug direct signal from SLUGGUARD sensor 6 SLUGGUARD Water Slug delayed Signal with on and off delay default 5 sec 1 sec 7 Fast Blink water alarm AFG or SLG 8 Alarm Fast Blink water alarm or overflow...

Page 48: ...cting the blue LED Flashlight The configuration of Digital outputs DO2 DO3 and DO4 is the same procedure than Relay Outputs 3 2 5 5 Config Backup By a click on Config Backup the submenu gets opened 3 2 5 5 1 Load Defaults By a click on Load Defaults you can set the system to defaults and delete the History A dialog will open It is possible to reset the Configuration of the CCS to defaults Click on...

Page 49: ...story The configuration reset affects on PIN Numbers They will be reset to defaults 3 2 5 5 2 Import Config To load a config file into CCS click Import Config More information in chapter 3 2 3 3 2 5 5 3 Export Config To store a config file as a backup or to transfer it to related CCS Silver systems click Export Config More Information in chapter 3 2 4 3 13 3 2 5 5 4 Reset History By a click on Res...

Page 50: ...ation Status telling if everything is O K or if there is an alarm Real clock for data logger and evaluation of logged data Info Dialog with information of the system IP settings and contact to the manufacturer Flow screen with actual flow rate and total fuelled volume for actual refuelling process Pressure screen with measured differential pressure across filter elements Setup Dialog will be opene...

Page 51: ...which is only visible if there actually is an alarm or warning The water detection screen You get information about the water contamination in the inlet and outlet and the current sensor status Also you get the averaged contamination during the refuelling process Condition for this feature is the availability of a pulsed or analog flow signal Override Button Water screen with measured water conten...

Page 52: ...35260 Stadtallendorf Manual_CCS_silver_Eng_ operation_version6 docx 3 2 6 1 States of CCS 3 2 6 1 1 O K Under normal circumstances all sensor signals pressure sensors flow signal and AFGUARD free water content are OK with no Alarm and Warning to inform about critical situations the CCS main screen should look as following ...

Page 53: ...Headline colour changes from green into yellow In this example there is a warning from the Outlet AFGUARD When Alarm levels are achieved headline colour changes from green yellow into red with blinking of screen The warning relay releases and the blue flashlight blinks slowly When multiple warnings occur then the headline changes colour from yellow to red the alarm relay releases the flashlight bl...

Page 54: ...one wire break or sensor errors the headline shows only the most critical one Also in the field of the sensor in the display the field blinks red and the text Broken Wire or Sensor Error is shown Please consider that the state in the sensor text fields shows the situation at the moment only If an error occurs and then it got fixed then it will only be shown in the headline Broken wire and sensor e...

Page 55: ...rier or connection between Please check cabling to make sure that all connections are OK Faulty alarm could either be caused by wrong pre setting of sensor signals In this case we recommend launching the installer again For the SLUGGUARD there is also a fail safe option which allows to show a wire break The SLUGGUARD should output 24V if everything is ok no water It should output 0V when it detect...

Page 56: ...ated using external reset button Please consider that a SLUGGUARD alarm could not be reset through hardware reset switch or reset button in the visualisation A SLUGGUARD alarm resets automatically when water gets drained at the SLUGGUARD mounting position By a press on the Reset Alarm button in the visualisation a PIN Dialog appears You are asked to enter a PIN For a reset you can insert the User ...

Page 57: ...ater Monitoring is active at the moment o No Water warnings Inlet Outlet o No Water alarm Inlet Outlet o No Water slug Inlet Outlet No SLUGGUARD alarm No wire breaks 𝐼 3 6𝑚𝐴 or sensor errors 𝐼 4𝑚𝐴 on all expected sensors No Overflow No Over DP If the listed conditions don t match the reset won t be accepted affecting to the state of the relays and depending on the reason of the alarm to the blue f...

Page 58: ...ed by the AFGUARD for the Inlet and the Outlet of the filter provided the corresponding sensor is installed The history can be shown on the screen The last 50 refuelling processes are stored on the intern memory of the CCS A USB drive is not required for showing the last 50 refuelling processes on the screen To call the history click on the History button on the dashboard The history page opens Yo...

Page 59: ...d and a history file is available you can download it by a click on Download Make sure your browser allows pop ups and supports File Transfer Protocol You can download the history also by entering the URL ftp 192 168 10 231 c history 3 2 6 4 Logfiles Since firmware 2020 10 28 you can comfortably download logfiles via web browser You don t need to unplug the USB drive anymore Click Logfiles If your...

Page 60: ...version6 docx When contacting FAUDI Aviation GmbH for service purposes please make sure to have data on info screen prepared These data are relevant to make online service available Also you see Firmware Version Number Serial No of the system and Uptime since last boot Clicking on the screen again or pressing the ESC button on your keyboard will bring you back to main screen ...

Page 61: ... time begins with a click on Start The screen shows Override active and a countdown Another Reset Button appears By a click on Reset the override mode will end immediately The standard behaviour of the system the relays and the lamp come back A click on Reset has the same behaviour than a hardware reset applied by a key switch You can also use the hardware reset to end the override Additionally al...

Page 62: ...every computer based software that is able to read CSV data or Excel files A simple text editor like Microsoft Notepad will do it as well For a more comfortable evaluation we recommend Excel or an equivalent tool Please insert the memory stick into a computer You can see following data structure There are two directories 1 history 2 logging 3 2 7 1 History Directory history contains logged data th...

Page 63: ...he begin of the refuelling process If the timestamp is wrong this can be a sign that the system time of the CCS is set wrong or the battery for the real time clock is discharged If you open a logfile with Notepad it looks like All sensors are optional If no sensor is connected to the system there will be no entry in the log In this case there is no DP Sensor and no SLUGGUARD connected You can down...

Page 64: ... program updates are due could be done using built in USB connector Please replace the memory stick against the one with updated software and close the housing You should only proceed in the way described when there is no process running Do not remove memory stick under process conditions when CCS Silver is working or logs should be done For further update instructions contact FAUDI Aviation senso...

Page 65: ... Time Year Current Date Month Day Hours Current Time Minutes Seconds PIN PIN User 00000000 Change and note PIN Admin 12345678 Units Pressure Unit bar Volume Unit Liters l Flow Rate Sensor Signal Sensor type Pulse Check flow meter documentation Measure range 20mA 10000 l min Check flow meter documentation Volume per Pulse 1 l Check flow meter documentation Attenuation time 5 sec 5 sec Pressure Sens...

Page 66: ...y Warning 9 sec 9 sec Multiple Warnings cause Alarm yes yes No Of Warnings for Alarm 2 2 Activate Alarms yes yes Level Alarm 30 ppm 30 ppm On Delay Alarm 9 sec 9 sec Level Water Slug 50 ppm 50 ppm On Delay Water Slug 4 sec 4 sec SLUGGUARD Available yes Check assembly Invert Signal yes yes On Delay 5 sec 5 sec Off Delay 1 sec 1 sec Filter Parameter Enable Overflow Alarm yes yes Rated Flow 5000 l mi...

Page 67: ... Modbus Modbus RTU Slave Address 4 4 Analog Output AO_3 N A optional AO_4 N A optional Relay Output REL_1 Alarm Inv unchangeable REL_2 Warning Inv unchangeable REL_3 Ready optional REL_4 Off optional Digital Output DO1 Flashlight unchangeable DO2 Off optional DO3 Off optional DO4 Off optional Water Monitoring Min Flow for Monitoring 50 l min 50 l min Min DP for Monitoring 0 05 bar 0 05 bar Off del...

Page 68: ...ed if Delay Begin of Monitoring and Minmum Fuel for Monitoring are unset Slow flashing 0 33Hz Water warning Fast flashing 2Hz Water Alarm multiple Warnings Alarm Slug Caused by an AFGUARD or SLUGGUARD Permanently off Overflow Alarm Over DP Alarm Sensor Error Sensor cable break CCS unpowered Override active No USB drive plugged invalid date and time battery empty Caution When you begin refuelling b...

Page 69: ...D 35260 Stadtallendorf Manual_CCS_silver_Eng_ operation_version6 docx The different flashing patterns are shown in the following diagrams 0 1 2 3 4 5 6 7 t sec Slow Flashing 0 33Hz Water Warning 0 1 2 3 4 5 6 7 t sec Fast Flashing 2Hz Water Alarm 0 1 2 3 4 5 6 7 t sec Permanently off 0 1 2 3 4 5 6 7 t sec Permanently on ...

Page 70: ...is http 192 168 10 231 8080 webvisu htm Only if the IP Address of the CCS didn t get changed since delivery in factory condition Otherwise replace the IP address in the shown URL The status LED of the CCS is blinking The CCS does not boot There is a failure of the device Usually this should not happen Note the blinking pattern and contact the manufacturer The CCS shows wrong values for analog sens...

Page 71: ... 72 FAUDI Aviation GmbH Scharnhorststraße 7 B D 35260 Stadtallendorf Manual_CCS_silver_Eng_ operation_version6 docx Wrong date and time never set correctly wrong timezone set date and time again in webvisu Battery empty Replace Battery type CR2032 and set date and time again ...

Page 72: ...ashboard 50 71 Differential Pressure 9 Flow Rate 10 28 40 45 65 Installer 22 Interlock 8 10 36 37 40 45 71 IP Address 43 68 71 Measure range 32 65 66 Monitoring 34 36 38 40 45 57 68 Network Settings 43 Off Delay 45 66 67 On Delay 33 45 66 67 68 PIN 11 14 24 25 26 40 41 42 49 50 56 65 Power Supply 8 11 Relay 8 11 Reset 8 11 39 48 49 51 56 58 61 Sensor Input 44 45 48 71 SLUGGUARD 5 8 10 11 35 40 45 ...

Reviews: