3.2.4.3.7 SLUGGUARD Settings
If you finished the setup for the AFGUARD Outlet the next sheet will be:
If you use the system with a SLUGGUARD® then make sure the available box is checked.
Otherwise uncheck the box.
For fail-safety, the Inverted logic is used and cannot be edited. This means, that the system
recognizes a water slug when there is a low level at the SLUGGUARD® Input.
For realizing a hysteresis, the system has an on and off delay of a few seconds for triggering
an alarm. This is preset to 5 and 1 sec and cannot be edited. Contact FAUDI Aviation if you
need different values.
If you are finished click Next >>.