7.2 OPERATING LOGICS
In all the logics, the STOP command has priority over
other commands and locks the automation system.
E
- SEMI-AUTOMATIC
Logic
E
only requires the OPEN command:
-
OPEN when the gate is closed causes it to open
-
OPEN when the gate is open causes it to close
-
OPEN during opening stops the gate
-
OPEN during closing reopens the gate
The CLOSE command always causes it to close.
A
- AUTOMATIC
Logic
A
only requires the OPEN command:
-
OPEN when the gate is closed causes it to
open. After the pause time, the gate closes
automatically.
-
OPEN when the gate is open in pause resets the
pause time. The pause time is also reset when
the closing photocells are triggered.
-
OPEN during opening is ignored.
-
OPEN during closing reopens the gate.
The CLOSE command always causes it to close.
b
- SEMI-AUTOMATIC B
Logic
b
requires the use of the OPEN and CLOSE
commands:
-
OPEN when the gate is closed causes it to open
-
CLOSE when the gate is open causes it to close
-
CLOSE during opening causes it to close
-
OPEN during closing reopens the gate
C
- DEAD-MAN
Logic
C
requires the use of maintained action OPEN
and CLOSE controls.
!
The control must be activated intentionally and the
gate must be visible.
-
OPEN maintained opens the gate
-
CLOSE maintained closes the gate
-
If the photocells are triggered, movement is
stopped.
7.3 SET-UP
The set-up procedure enables the limit switch posi-
tions to be memorised.
The set-up procedure must detect a stroke of between
0.5 and 12 m.
The system needs to be set-up:
-
When the automation system is first started
-
When the board has been replaced
-
Every time
L0
flashes on the display and the auto-
mation system is not working.
-
When you need to modify the stroke of the leaf
Set-up procedure
The SET-UP MUST be performed:
- with the mains power switched on
- with the automation system in manual mode
1. Select parameter
tL
in Basic Programming, the
display shows:
-
no
when the set-up has to be carried out (the
automation system is not working)
-
Y
when the set-up has already been carried
out. The set-up procedure can be carried out again
in order to modify the stroke.
2. Unlock the automation system.
3. Keep the
+
and
-
buttons pressed for approxi-
mately 3 seconds.
-
When
OP
flashes, release the buttons.
4. Open the leaf manually.
5. Press and then release the
+
+
button to memorise
the position.
-
CL
flashes on the display.
6. Close the leaf manually.
7. Press and then release the
+
+
button to memorise
the position.
8. The display indicates the automation system
closed status (
0 0
). The procedure has been
completed.
9. Restore automatic operation.