Basic function
Default
tL
SETUP
Acquire the limit switch positions.
See the relative section.
no
St
AUTOMATED SYSTEM STATUS
Y
save and exit from programming mode
no
exit from programming mode without
saving
Press
F
to confirm. After exiting, the display
indicates the status of the automation system:
00
Closed
01
Open
02
Stationary then opens
03
Stationary then closes
04
In
pause
05
Opening
06
Closing
07
verifying BUS 2easy devices
08
Fail Safe in progress
09
Pre-flashing and then opens
10
Pre-flashing and then closes
11
Forced opening in progress
12
Forced closing in progress
13
Sleep
Y
9
Advanced programming
Advanced function
Default
bo
MAXIMUM TORQUE AT INITIAL THRUST
Time in which the motor operates at maximum
power. Used for the initial thrust. Adjustable in steps
of a tenth of a second.
0.1
minimum
time
2.0
maximum
time
2.0
PF
PRE-FLASHING
no
disabled
OC
pre-flashing before every movement
cL
pre-flashing before closing
oP
pre-flashing before opening
PA
pre-flashing only at the end of the pause time
no
tP
PRE-FLASHING TIME (displayed only if
PF
is
not disabled):
Regulates the pre-flashing time in steps of 1 second.
01
minimum
pre-flashing
10
maximum
pre-flashing
03
Advanced function
Default
Ph
CLOSING PHOTOCELLS
The tripping of the photocells during closing causes
the gate to reverse (open).
Y
reverse only after the photocells have disen-
gaged
no
immediate
reverse
no
oP
OPENING PHOTOCELLS
Enable this function if you wish the opening
photocells to stop the movement and reverse the
gate during closing. Normally, with this function
disabled, if the photocells are triggered during
opening, movement resumes when they become
disengaged.
Y
immediate reverse during closing
No
movement resumes when disengaged
no
IP
PARTIAL REVERSE
The type of reverse (complete or partial) can be
selected when an obstacle is encountered or when
a safety edge or
the
encoder
is triggered.
Y
enable partial reverse. If an obstacle is de-
tected or a safety edge is triggered, the leaf reverses
for approximately 2 seconds and then stops.
no
disable partial reverse. If an obstacle is
detected, or a safety edge is triggered, the leaf
reverses completely and stops in the fully open or
fully closed position.
no
PO
PARTIAL OPEN
The partial opening width of the leaf can be adjust-
ed as a percentage of the total stroke of the gate.
Adjustable from 01 to 99 % in 1% steps.
01
minimum partial opening
99
maximum partial opening
50
t
CYCLE TIME (time-out)
Set a value greater than the time it takes for the
gate open or close completely.
Adjustable from 01 to 59 sec. in 1 second steps. The
display subsequently changes to minutes and tens
of seconds (separated by a point) and the time is
adjusted in 10 second steps, up to the maximum
value of 9.5 minutes.
E.g. If the display indicates
2.5
, the pause time is
2 min. and 50 sec.
When using a MASER/SLAVE config-
uration, the cycle time on the master
unit must be set taking into account
the movement times of both leaves.
9.5