Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
2.1.2 Flush Mounting (option)
• Analogue-addressable fire panel MAGPRO96 is available for flush mounting. The accessory set contains two special
hangers (see Figure 7) for flush wall mounting of the fire alarm panel on 25 mm thick drywall.
• Use given on Figure 6 dimensions to outline and to cut the mounting hole in the drywall.
• Fix the hinges on the back side of the gypsum plaster wall with the screws M4x30 cross slot DIN965 from the supplied
kit, as shown on Figure 7, Position 1.
• Route the external cables onto the back box, make off connection glands etc., BUT DO NOT make any connections
at this stage. ENTER THE MAINS CABLE THROUGH ITS OWN CABLE ENTRY POINT AND KEEP MAINS WIRING
AWAY FROM SYSTEM AND OTHER LOW VOLTAGE WIRING.
• Place the metal box in the mounting hole and fix as use the washers M4 DIN522 and the screws M4x40 cross slot
DIN7985 - Figure 7, Position 2.
• Connect the mains supply and earth to the power supply terminal (see Figure 17) BUT DO NOT apply the main electri
-
cal supply at this stage.
• Position the accumulator battery in an upright position and fix the metal clamp - Figure 10.
Figure 6. Dimensions of the metal box
Figure 7. Action sequence for flush
and the mounting hole.
mounting.
Figure 8. Flush mounting holes.
Main view of the fixed to the wall hinge and the bolts supporting the metal box.
HANGER
SCREWS FOR
HANGER FIXING
SCREWS FOR
FLUSH MOUNTING
METAL BOX
25mm THICK
DRYWALL
WASHER
HANGER
SCREWS FOR
HANGER
FIXING
WASHER
SCREWS FOR
FLUSH MOUNTING
METAL BOX
25mm THICK
DRYWALL