28
Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
MAGPRO-CP - Manual call point
Fig. Screen 9(d) - MAGPRO-CP manual call point.
On Fig. Screen 9(d) is shown the MAGPRO-CP (manual call point) settings screen. Choose the “MORE” button to enter
a screen with additional settings:
•
Event
- Every pressing of the button alternatively changes the type of the event generated with activation of the manual
call point:
- EVACUATE – The sounders will be activated immediately, as the set time delays Т1 and Т2 are ignored.
- ALARM – The set time delays Т1 and Т2 are active and the manual call point operated as an automatic
detector.
•
Led blink
- Button for changing the LED mode: ON Setting - The LED blinks at every query from the station; OFF
Setting - The LED does not show the dialogue cycle.
To save the new setting press the “Apply” button on the main screen of the device.
MAGPRO-WS - Wall mounted sounder
Fig. Screen 9(e) - MAGPRO-WS wall mounted sounder.
On Fig. Screen 9(e) is shown the MAGPRO-WS (wall mounted sounder) settings screen. Choose the “MORE” button
to enter a screen with additional settings:
•
Sound Level
- Every pressing of the button alternatively changes the sound level between HIGH/ LOW – as this
depends on the number of the connected sounders to the loop:
- HIGH – Set in those cases when the number of the connected sounders to the loop is up to 30 (WS and WSS).
- LOW – Set in those cases when the number of the connected sounders to the loop is up to 60 (WS and WSS).
At the bottom of the screen is shown in addition the Software Revision of the device in a separate field.
To save the new setting press the “Apply” button on the main screen of the device.