Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
29
MAGPRO-WSS - Wall mounted sounder and strobe
Fig. Screen 9(f) - MAGPRO-WSS wall mounted sounder and strobe.
On Fig. Screen 9(e) is shown the MAGPRO-WSS (wall mounted sounder and strobe) settings screen. Choose the
“MORE” button to enter a screen with additional settings:
•
Mode
- Press to choose from a list the mode of operation of the sounder:
Strobe lamp
(only the strobe light is active
in case of fire alarm event);
Sound
(only the sound is active in case of fire alarm event);
Sound/Strobe
(both the strobe
light and sound are active in case of fire alarm event);
•
Sound Level
- Every pressing of the button alternatively changes the sound level between HIGH/ LOW – as this
depends on the number of the connected sounders to the loop:
- HIGH – Set in those cases when the number of the connected sounders to the loop is up to 30 (WS and WSS).
- LOW – Set in those cases when the number of the connected sounders to the loop is up to 60 (WS and WSS).
At the bottom of the screen is shown in addition the Software Revision of the device in a separate field.
To save the new setting press the “Apply” button on the main screen of the device.
MAGPRO-DBS - Base with sounder
Fig. Screen 9(g) - MAGPRO-DBS base with sounder.
On Fig. Screen 9(g) is shown the MAGPRO-DBS (base with sounder) settings screen. Choose the “MORE” button to
enter a screen with additional settings:
•
Sound Level
- Every pressing of the button alternatively changes the sound level between HIGH/ LOW – as this
depends on the number of the connected sounders to the loop:
- HIGH – Set in those cases when the number of the connected sounders to the loop is up to 30 (DBS and DBSS).
- LOW – Set in those cases when the number of the connected sounders to the loop is up to 100 (DBS and DBSS).
At the bottom of the screen is shown in addition the Software Revision of the device in a separate field.
To save the new setting press the “Apply” button on the main screen of the device.