2.2.8 Connecting of the accumulator battery
Figure 18. Connecting the accumulator battery to the main power source.
·
Connect the red cable to the positive pole of the battery, and the black cable - to the negative battery pole.
Both of the cables are connected to the battery by means of a flat terminal lug Ø5mm.
ATTENTION:
The connection between the accumulator battery and the main power source has some special
features. It is strongly recommended to use only battery with electrical characteristics and dimensions pointed from
the manufacturer. Before connecting to the power source check the polarity of the battery. The battery cannot power
up the panel before the mains supply has been switched on. Connect the battery after the mains supply is turned on. If
the battery is new it will take a few hours before its complete charging!
The charging of the accumulator battery is done at maximum current I=2A and charging voltage U < 13,8V.
2.3 Main Board Schematics
The main board is situated on the back side of the front cover. On the main board is factory integrated a control module
- uPC Module, for control of the panel functions and operations.
ATTENTION: Adjustment on the main board can be done from an authorized personnel only!
Figure 19. Main Board with integrated Control Module.
Sealed lead acid type
rechargeable battery
12V / 18Ah
Red
Black
Main
Power
Source