3.4 Zones
Choose in sequence from the Main menu screen
System - Programming - Zones.
The MAGPRO96 addressable fire panel avails of 96 zones. The
FIRE
and
PREALARM
conditions are indicated by the
help of the LED of the corresponding zone. In the
PREALARM
condition - the respective zone LED blinks and a warning
message is displayed on the screen. If there is a second activation of devices in the same zone an alarm message FIRE
is generated for the respective zone. To enter the submenu for zone configuration, chose “
Zones
” button from Program
-
ming menu - Fig. Screen 3. The general view of the zone configuration menu is shown on Fig. Screen 13.
Fig. Screen 13.
3.4.1 button for Selecting the Zone Number
The zone number can be selected in sequence or directly, which can than be monitored.
3.4.2 Active Field for Introducing Zone Name
Choose the button to enter the screen, for introducing the zone name, which shall not exceed 40 digits together with the
spaces. Verify the information with the
button.
3.4.3 Zone Group
The zones in MAGPRO96 addressable fire alarm panel can be organized for operation in separate groups. The maxi
-
mum number of the permissible groups is 48. By default all zones are not associated to a group number – value 0 is
set.
3.4.4 button for Zone Mode Change
Each zone has three working modes:
NORMAL
,
2DEVICES
and
DOUBLE
.
•
In
NORMAL
mode any detector activation within the system generates an alarm event to the respective zone.
•
In
2 DEVICES
mode any detector activation within the system generates a PREALARM event to the respective zone,
but also awaits the activation of another detector from the same zone to generate a FIRE signal. The RESET command
shall disable the FIRE and PREALARM events. If during 5 minutes there is no other fire alarm signal from other detector
in the zone the FIRE alarm will be ignored. The operation of a zone in 2 DEVICES action mode is shown in the examples
below.
•
In
DOUBLE
mode any detector activation within the system generates a PREALARM event to the respective zone, but
will awaits a second fire signal from the same detector to generate a FIRE signal. The RESET command shall disable
the FIRE and PREALARM events. If during 5 minutes there is no other fire alarm signal from the same detector in the
zone the FIRE alarm will be ignored.
3.4.5 Sounder Delay (T2)*
The delay can be within an interval of 0-540 sec.
In case of activation of more than one zone, the delays to the outputs are caused by the zone with shorter delays.
3.4.6 Fire output Delay (T2)*
The delay can be within an interval of 0-540 sec.
In case of activation of more than one zone, the delays to the outputs are caused by the zone with shorter delays.
3.4.7 Fire protection Output Delay (T2)*
The delay can be within an interval of 0-540 sec.
In case of activation of more than one zone, the delays to the outputs are caused by the zone with shorter delays.
3.4.8 Enable/Disable Zone button
Button for Enabling / Disabling zones.
All changed parameters are confirmed and saved by pressing the APPLY button in the upper left cor
-
ner of the screen.
* Note:
Т2 presents times for individual output delay setting. See APPENDIX E - Two steps of alarming algorithm.