Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
47
The following parameters are available to set:
•
Sounders Mode
– Press to change the sounders operation mode. The options are displayed in a separate screen:
• Common - All sounders will be activated with no sense of zone to which they are connected.
• Zonal - Only the sounder of the zones with alarm condition will be activated.
•
Evacuation Timeout
– The firld is active only in ZONAL operation mode. The EVACUATION TIMEOUT is a time delay
until evacuation of the site. Enter the submenu and use the up/ down arrow buttons to set a DELAY time from 0 to 10
minutes. In a fire situation only the sounder of the zone(s) with alarm condition will be activated. After the set evacuation
timeout delay is over the sounders in the whole site are activated also.
•
Alarm Tone
– Set the alarm type sound. Use the arrow buttons to select a number from 1 to 32 for the alarm sound –
the reference parameters for the selected sound are listed in the description field. To play the set sound tone press the
field with the sound description.
•
Evacuation Tone
– Set the evacuation type sound. Use the arrow buttons to select a number from 1 to 32 for the
evacuation sound – the reference parameters for the selected sound are listed in the description field. To play the set
sound tone press the field with the sound description.
Confirm the settings with ‘Apply’ button.
3.7.5 Call point Mode
Choose button
Call points Mode
from
Panel
menu to enter in this submenu - see Fig. Screen 18. The Installer has a
possibility to choose the alarm mode if a call point is been activated - Common or Zonal. For this purpose on a separate
screen are displayed buttons, as:
• Common
- A general alarm will be activated with no sense of to which zone the call point is been connected.
• Zonal
- Only an alarm in the zone where the call point is been connected.
Fig. Screen 24 - Choosing a Call points Mode.
All changed parameters are confirmed and saved by pressing the APPLY button in the upper left corner of the
screen.
3.7.6 Language selection
Here the Installer can choose between the available languages in the system.
3.7.7 Delay (T1)
Here the Installer can set a common time delay for activation for all outputs (from 0 to 60 seconds).
See also APPENDIX E - “Two steps of alarming” working algorithm.
3.7.8 Printer Menu
Here the Installer can choose the model of heat printer connected to the panel. To possible models are available:
•
KAFKA
•
EP1000
The current set mode is displayed with dark letters on a white inactive button. To change the printer model press the
other button and then press “Apply“ button.
3.8 Restore Defaults
In this menu the installer performs reset to default settings of the system configuration. The panel will ask for confirma
-
tion of the action.