24
Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
Fig. Screen 7 - LOOP (Loop controller) -
Example for adding/ removing of new periphery device
Note:
After choosing the
SAvE
button it disappears from the screen and the status of the device from
NEW
changes
to
NORMAL
.
3.3.2 Loop Devices
To enter the submenu for programming of the loop devices parameters from “
Device
” menu choose button “
Loop De-
vices
” - Fig. Screen 4.
Attention: The searching for new loop devices is done only when the MAGPRO96-L250
loop controller has been added to the configuration.
When a new loop device is found (missing in the configuration) the message “
NEW LOOP DEVICES FOUND
” will be
generated, as well as the number of detected devices. The message is generated by loops. Adding a new device to the
configuration is accomplished with the
APPLY
command from the specific device menu or with the help of the general
SAVE command from the
Programming
menu. Any device, which has not been added to the configuration, cannot gen
-
erate messages. In case of removal of a loop device, the panel generates a ”
LOOP DEVICE FAULT
” message. When
a newly detected device is removed, the panel reduces the number of the new devices and if their number is 0 it shall
extinguish the “
NEW LOOP DEVICES FOUND
” message. Removing the device from the configuration is accomplished
with the
REMOVE
command in the menu for the specific device.
Where in abundance, it is possible for device addresses to double along the loops (see also
item 2.2.6 Maximum per-
missible cable length
). In such cases the message “
DOUBLE ADDRESS
” will be displayed along with the problem
address. To determine the loop devices with doubled addresses, choose in sequence the loop number and doubled
address. In the left bottom of the screen press the LED button - the LEDs of all devices recorded with this address will
light on. That ensures quick finding all devices with one and the same address and correction with new address. The
next pressing of the LED button will light off the LEDs of the devices.
Should a different device type appear at the address of a saved device, the panel will generate “
LOOP DEVICE TYPE
ERROR
”. For MAGPRO96-L250 loop controller first you need to remove wrong and then to save the new type of the
device.
!
MAGPRO