Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
51
4.5.2 Fire output Delay
Choose “
Fire Br. Delay”
button from “Output Delay” Menu - Fig. Screen 30 to enter the submenu for fire output delay
introduction (the screen is the same as those for sounder delay introduction).
A delay can be added before the sounders are turned on (fire output). This provides the possibility of checking the au
-
thenticity of the alarm before the sounders are turned on (an official visits the site and inspects for fire).
The delay can be:
ON
,
OFF
or
Schedule
. In Schedule mode the initial hour and minutes (the time when the delay is
activated) and the end hour and minutes (the time when the delay is deactivated) are introduced. The times are set for
every day of the week. During turned on “
Delay
” the LED is active.
4.5.3 Fire Protection Delay
Choose “
Fire Pr. Delay
” button from “Output Delay” Menu - Fig. Screen 30 to enter the submenu for fire protection delay
introduction (the screen is the same as those for sounder delay introduction).
A delay can be added before the fire protection system is turned on. This provides the possibility of checking the authen
-
ticity of the alarm before the sounders are turned on (an official visits the site and inspects for fire).
The delay can be:
ON
,
OFF
or
Schedule
. In Schedule mode the initial hour and minutes (the time when the delay is
activated) and the end hour and minutes (the time when the delay is deactivated) are introduced. The times are set for
every day of the week. During turned on “
Delay
” the LED is active.
All changed parameters are confirmed and saved by pressing the APPLY button in the upper left cor
-
ner of the screen.
4.6 LOG-file view
Choose “
View Log
” from the
Maintenance
Menu to enter in a screen for viewing the recorded events in the system. The
addressable fire panel MAGPRO96 can show maximum 10 240 events, which could be viewed by date or number - Fig.
Screen 32.
Fig. Screen 32.
4.7 Testing
The addressable fire panel MAGPRO96 has an option for testing of the operability of the system. Entering the TEST
menu the installer can maintain:
•
Zone Testing
•
Indication (internal buzzer and LEDs operation) Testing
•
Device Testing
•
Sounder Output Testing
To make a test, choose the “
Test
” button from Programming Menu - Fig. Screen 25. On the displayed screen the user/
installer could choose which test to perform - Fig. Screen 33.