Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
41
3.6 Outputs
To enter the submenu for outputs configuration choose “
Outputs
” button from Programming menu - Fig. Screen 3. The
general view of the menu for inputs configuration is shown on Fig. Screen 16.
Fig. Screen 16 - Menu for introducing output parameters.
3.6.1 Type of output
By pressing the button for output type a new screen is displayed from which can be chosen the following types:
Action
Event
3.6.2 Submenus for setting of output type parameters
Depending on the type of output after choosing the button
MORE
could be programmed the parameters of every output
type. The information is displayed on a separate screen. There can be programmed the following parameters:
•
PERIPHERY
-
Select if the input is a periphery device. Choose the
MORE
button:
-
Address of periphery device
.
Enter an address number from 1 to 10.
-
Output of periphery device
. The button have two states - ON and OFF, according the type of the device. Enter
a periphery device output number.
•
LOOP
-
Select if the input is a loop device. Choose the
MORE
button
-
Address of loop device
.
Enter an address number from
1 to 250.
-
Loop number
. Enter the loop number.
-
Channel
. Enter a serial number of an output accessible in the device.
Note: It is possible to enter addresses only of loop devices, which are OuTPuT type: sirens, input-outputs
modules! If the device if not an OuTPuT type a message is shown: “This device can not be used as Output!”
•
NETWORK
- Panel / repeater number and output number, to which the output shall be attached. Choose the
MORE
button. Set the parameters in the screen “
OUTPUT Parameters - network”:
- OUTPUT Number.
Enter a number from 1 to 128.
-
PANEL/ REPEATER Number.
Enter a number from 1 to 32.
•
ACTION
- Choose the
MORE
button. Set the parameters in the screen “
OUTPUT Parameters - Actions”.
Here you can
choose the actions activating the output from the list on the screen:
-
Silence Buzzer
-
Silence Alarm
- Reset
- Evacuation
- Delay Override
- Class Change -
To use the class change function, connect the terminals of a switch with normally open contacts
to the module terminals. The working mode of the sounders at input activation is:
- when the switch is pressed - one second sounders on, one second sounders off;
- when the switch is released - the sounder is off.