Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
27
•
Led blink
- Button for changing the LED mode: ON Setting - The LED blinks at every query from the station; OFF
Setting - The LED does not show the dialogue cycle.
•
Day Alarm Level, temp*
- Setting the day class temperature for operation.
•
Night Alarm Level, temp.*
- Setting the night class temperature for operation.
* There are 3 temperature classes for operation: A1R (58
º
, RoR), A2S (60
º
), BS (75
º
). To change the class simple press
the active button next to the field and choose a new level from the list.
To save the new setting press the “Apply” button on the main screen of the device.
MAGPRO-HSD1 - Combined optical-smoke and heat detector
Fig. Screen 9(c) - MAGPRO-HSD1 fire detector.
On Fig. Screen 9(c) is shown the MAGPRO-HSD1 (addressable optical smoke and temperature RoR detector) set
-
tings screen. Choose the “MORE” button to enter a screen with additional settings:
•
Smoke (%)/ Heat (
°
C)
- Press the button to enter in a new screen for checking of the following current parameters:
- Smoke: Shows in percent the current level of smoke in the detector’s smoke chamber
- Pollution: Shows in percent the current level of pollution in the detector’s smoke chamber.
- T fire – Shows the operating temperature of the detector, in degrees centigrade.
- Т – Shows the current temperature in the room, in degrees centigrade.
•
Led blink
- Button for changing the LED mode: ON Setting - The LED blinks at every query from the station; OFF
Setting - The LED does not show the dialogue cycle.
•
Day Alarm Level
. Set here the sensitivity level of the optical part of the detector and enable/ disable the heat part.
These settings are valid for the daytime:
-
Sensitivity level
.
There are 4 levels for setting of alarm level sensitivity for the optical part: High, Normal,
Middle and Low. To change the level of sensitivity simple press the active button next to the field and choose
a new level from the list.
-
Heat part
.
In addition for this device only the installer can enable or disable the heat part of the detector. The
state of the heat part can be changed with pressing the button.
•
Night Alarm Level
.
Set here the sensitivity level of the optical part of the detector and enable/ disable the heat part.
These settings are valid for the nighttime. Operation of setting is the same with those for the day alarm level.
Attention: It is not allowed disabling the temperature and the optical parts at the same time!
To save the new setting press the “Apply” button on the main screen of the device.