Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
11
2.2.4 Connecting devices to the Outputs Module
The monitored outputs SND, FIRE R, FIRE P and FAULT R, at activation, provide
24VDC@0,3A to the load connected between them and GND (the earthing point of the
panel).
It is necessary to connect in parallel to the last device in the loop a 10k terminate resis
-
tor, so to ensure that the panel is able to detect any break or short circuit in the loop -
see Fig. 12.
Figure 12. Example for connecting of end device (an illuminated exit sign)
to the Monitored FIRE Output.
To the monitored output
SND
could be connected several sounders - Figure 13. The maximum number of sounders that
could be connected in the circuit, depends on their total current consumption, which must not exceed 0,3A.
Before connecting the last sounder in the circuit, parallel to it
must be added
resistor 10k.
Figure 13. Connecting of sounders.
!