Section 3: HART commissioning
April 2014
6.
Select
1 Enable
to enable Thermocouple Diagnostic and press
ENTER
.
7.
Decide if you would like to change the trigger level or the sensor you are configuring. If
so, choose
1 Yes
. If not, choose
2 No. Return to Main Screen
.
8.
IF YES
: Select a trigger level for the sensor you are configuring and press
ENTER
.
Choose between a fixed 5K Ohms, Baseline x 2, Baseline x 3, and Baseline x 4.
9.
Review the summary provided on the communicator and press
OK
when satisfied or
ABORT
to exit.
10.
Decide if you would like to reset the baseline resistance of the thermocouple you are
configuring. If so, choose
1 Yes
. If not, choose
2 No. Return to Main Screen
.