136
Reference Manual
00809-0100-4021, Rev GC
Section 3: HART commissioning
April 2014
Save data from device to
configuration memory
Prompts user to press SAVE softkey to initiate a device-to-memory transfer.
Saving data to configuration memory
Data is being transferred from a device to configuration memory.
Sending data to device
Data is being transferred from configuration memory to a device.
There are write only variables which
have not been edited. Please edit
them.
There are write-only variables that have not been set by the user. These variables
should be set or invalid values may be sent to the device.
There is unsent data. Send it before
shutting off?
Press YES to send unsent data and turn the Field Communicator off. Press NO to turn
the Field Communicator off and lose the unsent data.
Too few data bytes received
Command returns fewer data bytes than expected as determined by the device
description.
Transmitter fault
Device returns a command response indicating a fault with the connected device.
Units for <variable label> has
changed. Unit must be sent before
editing, or invalid data will be sent.
The engineering units for this variable have been edited. Send engineering units to
the device before editing this variable.
Unsent data to online device. SEND or
LOSE data
There is unsent data for a previously connected device which must be sent or
thrown away before connecting to another device.
Use up/down arrows to change
contrast. Press DONE when done.
Gives direction to change the contrast of the Field Communicator display.
Value out of range
The user-entered value is either not within the range for the given type and size of
variable or not within the min/max specified by the device.
<message> occurred reading/writing
<variable label>
Either a read/write command indicates too few data bytes received, transmitter
fault, invalid response code, invalid response command, invalid reply data field, or
failed pre- or post-read method; or a response code of any class other than SUCCESS
is returned reading a particular variable.
<variable label> has an unknown
value. Unit must be sent before
editing, or invalid data will be sent.
A variable related to this variable has been edited. Send related variable to the
device before editing this variable.
(1) Variable parameters within the text of a message are indicated with <variable parameter>. Reference to the name of another message is identified by [another
message].
Table 3-3. Field Communicator Error Warning Descriptions – HART
(1)
Message
Description
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......