Reference Manual
00809-0100-4021, Rev GC
Appendix B: Product Certifications
April 2014
I6
CSA Intrinsic Safety and Division 2
Certificate: 1242650
Standards Used: CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA-C22.2 No. 94-M91, CSA
Std C22.2 No. 142-M1987, CAN/CSA-C22.2 No. 157-92, CSA Std C22.2 No. 213-M1987;
Markings: Intrinsically Safe for Class I Groups A, B, C, D; Class II, Groups E, F, G; Class III;
[HART only zone markings]: Intrinsically Safe for Class I Zone 0 Group IIC;
T4(–50 °C
T
a
60 °C); Type 4X; Suitable for Class I, Div. 2, Groups A, B, C, D;
[HART only zone markings]: Suitable for Class I Zone 2 Group IIC; T6(–60 °C
T
a
60 °C);
T5 (–60 °C
T
a
85 °C); when installed per Rosemount drawing 03144-5076;
K6
CSA Explosionproof, Intrinsic Safety and Division 2
Certificate: 1242650
Standards Used: CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std C22.2 No. 30-M1986;
CAN/CSA-C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CAN/CSA-C22.2 No.
157-92, CSA Std C22.2 No. 213-M1987;
Markings: Explosionproof for Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III;
[HART only zone markings]: Suitable for Class I Zone 1 Group IIC; Intrinsically Safe for
Class I Groups A, B, C, D; Class II, Groups E, F, G; Class III;
[HART only zone markings]: Suitable for Class I Zone 0 Group IIC; T4(–50 °C
T
a
+60 °C);
Type 4X; Suitable for Class I, Div. 2, Groups A, B, C, D;
[HART only zone markings]: Suitable for Class I Zone 2 Group IIC; T6(–60 °C
T
a
60 °C);
T5(–60 °C
T
a
+85 °C); when installed per Rosemount drawing 03144-5076;
Europe
E1
ATEX Flameproof
Certificate: FM12ATEX0065X
Standards Used: EN 60079-0: 2012, EN 60079-1: 2007, EN 60529:1991 +A1:2000
Markings:
II 2 G Ex d IIC T6…T1 Gb, T6(–50 °C
T
a
40 °C), T5…T1(–50 °C
T
a
60
°C);
See
at the end of the Product Certifications section for process temperatures.
Special Conditions for Safe Use (X):
1.
See certificate for ambient temperature range.
2.
The non-metallic label may store an electrostatic charge and become a source of
ignition in Group III environments.
3.
Guard the LCD display cover against impact energies greater than 4 joules.
4.
Consult the manufacturer if dimensional information on the flameproof joints is
necessary.
I1
ATEX
Intrinsic
Safety
Certificate: BAS01ATEX1431X [HART]; Baseefa03ATEX0708X [Fieldbus];
Standards Used: EN 60079-0: 2012; EN 60079-11: 2012;
Markings: HART:
II 1 G Ex ia IIC T5/T6 Ga; T6(–60 °C
T
a
50 °C), T5(–60 °C
T
a
75
°C); Fieldbus:
II 1 G Ex ia IIC T4 Ga; T4(–60 °C
T
a
60 °C)
See
at the end of the Product Certifications section for Entity Parameters.
Special Conditions for Safe Use (X):
1.
When fitted with the transient terminal options, the equipment is not capable of
passing the 500 V insulation test. This must be taken into account during installation.
2.
The enclosure may be made from aluminum alloy with a protective polyurethane paint
finish; however, care should be taken to protect it from impact or abrasion when
located in Zone 0.
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......