Section 3: HART commissioning
April 2014
LCD display message
The LCD display on the transmitter will display a message
WARN SNSR 2 FAIL; WARN AV DEGRA
as
well as the output of the average temperature. Because Sensor 2 has failed, this average
temperature output is the value of Sensor 1 only.
After the sensor has been repaired or replaced, the LCD display warning message will clear and
display the output of the primary variable.
DeltaV message
Alarms will show up on the bottom toolbar, as shown below:
To view the alarm, simply click on the device on the toolbar. A faceplate with further information
on the active alarms will appear. It will show an
ADVISE Sensor Summary
, and a
FAILED Sensor 2
Open
.
Note
For all of these alarms to appear in DeltaV, all alarms in DeltaV must be configured to
WARNING
status.