146
Reference Manual
00809-0100-4021, Rev GC
Section 4: F
OUNDATION
fieldbus Configuration
April 2014
Foundation™ fieldbus configuration
FAILED_PRI
Designates the alerting priority of the FAILED_ALM, see
default is 0, and the recommended values are between 8 and 15.
FAILED_ACTIVE
This parameter displays the active alarms. Only the highest priority alarm will be displayed. This
priority is not the same as the FAILED_PRI parameter described above, but is hard coded within
the device and is not user configurable.
FAILED_ALM
Alarm indicating a failure within a device which makes the device non-operational.
MAINT_ALARMS
A maintenance alarm indicates the device, or some part of the device, needs maintenance soon.
If the condition is ignored, the device will eventually fail. There are five parameters associated
with MAINT_ALARMS:
MAINT_ENABLED
The MAINT_ENABLED parameter contains a list of conditions indicating the device, or some part
of the device, needs maintenance soon.
Below is a list of the conditions, with the highest priority first.
1.
Primary Value Degraded
2.
Secondary Value Degraded
3.
Configuration Error
4.
Calibration Error
MAINT_MASK
The MAINT_MASK parameter masks any of the failed conditions listed in MAINT_ENABLED. A bit
on means that the condition is masked out from alarming and will not be reported.
MAINT_PRI
MAINT_PRI designates the alarming priority of the MAINT_ALM, see
. The default is 0 and the recommended values is 3 to 7.
MAINT_ACTIVE
The MAINT_ACTIVE parameter displays which of the alarms is active. Only the condition with
the highest priority will be displayed. This priority is not the same as the MAINT_PRI parameter
described above. This priority is hard coded within the device and is not user configurable.
MAINT_ALM
An alarm indicating the device needs maintenance soon. If the condition is ignored, the device
will eventually fail.
Advisory alarms
An advisory alarm indicates informative conditions that do not have a direct impact on the
device's primary functions. There are five parameters associated with ADVISE_ALARMS. They
are described below.
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......