153
Reference Manual
00809-0100-4021, Rev GC
Section 4: F
OUNDATION
fieldbus Configuration
April 2014
Foundation™ fieldbus configuration
BLK_TYPE_#
Enter the Block Type of the function block containing the parameter to be displayed. This
parameter is generally selected by a drop-down menu with a list of possible function block types
(e.g. Transducer, PID, AI, etc.).
PARAM_INDEX_#
The PARAM_INDEX_# parameter is selected by a drop-down menu with a list of possible
parameter names, based upon availability in the function block type selected. Choose the
parameter to be displayed.
CUSTOM_TAG_#
The CUSTOM_TAG_# is an optional user-specified tag identifier that can be configured to be
displayed with the parameter instead of the block tag. A tag of up to five characters can be
entered.
UNITS_TYPE_#
The UNITS_TYPE_# parameter is selected by a three option drop-down menu: AUTO, CUSTOM,
or NONE. AUTO is only when the parameter to be displayed is pressure, temperature, or percent.
For other parameters, select CUSTOM, making sure to configure the CUSTOM_UNITS_#
parameter. Select NONE if the parameter should be displayed without associated units.
CUSTOM_UNITS_#
Specify custom units to be displayed with the parameter, entering up to six characters. To
display Custom Units the UNITS_TYPE_# must be set to CUSTOM.
4.7.2
LCD display transducer block diagnostics
Table 4-8. LCD display Transducer Block BLOCK_ERR messages
Condition name and description
Other
Out of Service: The actual mode is out of service
Symptom
Possible causes
Recommended action
The LCD display displays “DSPLY#INVLID.” Read the
BLOCK_ERR and if it says “BLOCK CONFIGURATION”
perform the Recommended Action
One or more of the display
parameters are not configured
properly
See
.
The Bar Graph and the AI.OUT readings do not
match
The OUT_SCALE of the AI block is not
configured properly
See
and
.
“3144P” is being displayed or not all of the values
are being displayed
The LCD display block parameter
“DISPLAY_PARAMETER_SELECT” is
not properly configured
See
.
The display reads OOS
The resource and or the LCD display
Transducer block are OOS
Verify that both blocks are in
“AUTO”.
The display is hard to read
Some of the LCD display segments
may have gone bad
See
; if some of the
segment is bad, replace the LCD
display.
Device is out of the temperature limit
for the LCD display. (-20 to 85 °C)
Check ambient temperature of the
device.
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......