Section 3: HART commissioning
April 2014
Resetting Active Sensor Drift Alerts: Fast Keys 1-1-1
1.
Select
1 Overview
.
2.
Select
1 Device Status: (Maintenance or Failed)
.
3.
Select
1 Refresh Alerts
.
3.8
Device output configuration
Device output configuration contains PV range values, alarm and saturation, HART output, and
LCD display options.
3.8.1
PV range values
Field communicator
The
PV URV
and
PV LRV
commands, found in the
PV Range Values
menu screen, allow the user to
set the transmitter’s lower and upper range values using limits of expected readings. See
for unit and range setting limits. The range of expected readings is defined by
the Lower Range Value (LRV) and Upper Range Value (URV). The transmitter range values may
be reset as often as necessary to reflect changing process conditions. From the
PV Range Values
screen select
1 PV LRV
to change the lower range value and
2 PV URV
to change the upper range
value.
HART 5 Fast Keys
2, 2, 5, 5
HART 7 Fast Keys
2, 2, 5, 5
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......