Reference Manual
00809-0100-4021, Rev GC
Appendix A: Reference Data
April 2014
Standard configuration
Both standard and custom configuration settings may be changed. Unless specified, the
transmitter will be shipped as follows:
Standard configuration
Description
4 mA value / Lower Range (HART / 4–20 mA)
0 °C
20 mA value / Upper Range (HART / 4–20 mA)
100 °C
Damping
5 seconds
Output
Linear with temperature / F
OUNDATION
fieldbus
Failure Mode (HART / 4–20 mA)
High
Line Voltage Filter
60 Hz
Software Tag
If a Hardware Tag is specified it will be entered into
the software tag as well. Otherwise it will be left
blank.
Optional Integral Meter
Units and mA / Sensor 1 units
Single sensor option
Description
Sensor Type
4-wire Pt 100
= 0.00385 RTD
Primary Variable (HART / 4–20 mA)
Sensor 1
Secondary Variable
Terminal (Body) Temperature
Tertiary Variable
Not Available
Quaternary Variable
Not Available
Dual sensor option
Description
Sensor Type
Two 3-wire Pt 100
= 0.00385 RTD
Primary Variable (HART / 4–20 mA)
Sensor 1
Secondary Variable
Sensor 2
Tertiary Variable
Terminal Temperature
Quaternary Variable
Not Used
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......