Reference Manual
00809-0100-4021, Rev GC
Appendix A: Reference Data
April 2014
191
Appendix A
Reference data
HART® and Foundation™ fieldbus specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 191
HART / 4–20 mA specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 198
Foundation fieldbus specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 200
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 203
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 206
Spare parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 211
A.1
HART
®
and F
OUNDATION
™
fieldbus specifications
A.1.1
Functional specifications
Inputs
for sensor options.
Output
2-wire device with either 4–20 mA/HART, linear with temperature or input. Completely digital
output with F
OUNDATION
fieldbus communication (ITK 4.5 compliant).
Isolation
Input/output isolation tested up to 500 V rms (707 Vdc).
Humidity limits
0–99% Relative Humidity (Non-condensing).
Update time
Approximately 0.5 seconds for a single sensor (1 second for dual sensors).
A.1.2
Physical specifications
Conduit connections
The standard field mount housing has ½–14 NPT conduit entries. Additional conduit entry types
are available, including PG13.5 (PG11), M20 X 1.5 (CM20), or JIS G ½. When any of these
additional entry types are ordered, adapters are placed in the standard field housing so these
alternative conduit types fit correctly. See
Dimensional drawings on page 203
for dimensions.
Materials of construction
Electronics Housing
Low-copper aluminum or CF-8M (cast version of 316 Stainless Steel)
Paint
Polyurethane
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......