60
Reference Manual
00809-0100-4021, Rev GC
Section 3: HART commissioning
April 2014
After resetting Hot Backup, the device status in the
Process Variable Overview
section of the DTM
will change from
Maintenance
to
Advisory
, as shown below.
Investigate this advisory alert by clicking Investigate in the blue device status box. Another
screen will display the active alerts, indicating
ADVISORY Configuration Changed
, as shown below.
To clear this advisory, simply choose
Clear Config Changed Flag
and follow the steps.