Reference Manual
00809-0100-4021, Rev GC
Section 3: HART commissioning
April 2014
6.
When prompted, choose
1 Yes
to disable Hot Backup. To reconfigure Hot Backup,
choose
2 No
.
7.
When prompted, choose which variable you would like as your primary variable (PV)
and choose
ENTER
. With Hot Backup disabled, the PV may be
Sensor 1 Temperature
,
Sensor 2 Temperature
,
Differential Temperature
,
Average Temperature
, or
First Good
Temperature
.