154
Reference Manual
00809-0100-4021, Rev GC
Section 4: F
OUNDATION
fieldbus Configuration
April 2014
Foundation™ fieldbus configuration
4.8
Hot Backup
™
transducer
Note
Primary Value 1 indicates Sensor 1 value and Primary Value 2 indicates Sensor 2 value.
Sensor 1 as a default sensor
Sensor 2 as a default sensor
Hot Backup parameters
Sub parameter
Description
Values to be set
FEATURE_CONFIG
FEATURE_ENABLE
Select the feature
Hot Backup
DEFAULT_SENSOR
Set default sensor, either Sensor 1 or Sensor 2
Sensor 1
UNIT_INDEX
Set unit of measurement
Deg C
FEATURE_VALUE
FEATURE_STATUS
This value changes dynamically
N/A
FEATURE_VAL
This value changes dynamically
N/A
Primary value
1 status
Primary
value 2 status
FEATURE_VAL /
FEATURE_STATUS
Recommended action
Good
Good
Primary Value 1/Good
No Error
Good
Uncertain
Primary Value 1/Good
Sensor 2 out of operating range or Sensor 2 Degraded.
Good
Bad
Primary Value 1/Good
Sensor 2 Open or short or Beyond operating range
Uncertain
Good
Primary Value 2/Good
Hot Backup Active and (Sensor 1 out of operating range or
Sensor 1 Degraded)
Uncertain
Uncertain
Primary Value 1/Uncertain
((Sensor 1 out of operating range or Sensor 1 Degraded)
and (Sensor 2 out of operating range or Sensor 2
Degraded)) or Drift Alert
Uncertain
Bad
Primary Value 1/Uncertain
(Sensor 1 out of operating range or Sensor1 Degraded)
and (Sensor 2 Open or short or Beyond operating range)
Bad
Good
Primary Value 2/Good
Hot Backup Active and Sensor 1 open or short or Beyond
operating range
Bad
Uncertain
Primary Value 2/Uncertain
Hot Backup Active and Sensor 1 open or short or Beyond
operating range and (Sensor 2 out of operating range or
Sensor 2 Degraded)
Bad
Bad
None (Last good value)/Bad
Hot Backup Active and (Sensor 1 open or short or beyond
operating range) and (Sensor 2 open or short or beyond
operating range)
Primary value
1 status
Primary
value 2 status
FEATURE_VAL /
FEATURE_STATUS
Recommended action
Good
Good
Primary Value 2/Good
No Error
Good
Uncertain
Primary Value 1/Good
Hot Backup Active and Sensor 2 out of operating range or
Sensor2 Degraded
Good
Bad
Primary Value 1/Good
Hot Backup Active and Sensor 2 Open or short or Beyond
Operating range
Uncertain
Good
Primary Value 2/Good
Sensor 1 out of operating range or Sensor 1 Degraded
Uncertain
Uncertain
Primary Value 2/Uncertain
((Sensor 1 out of operating range or Sensor 1 Degraded)
and (Sensor 2 out of operating range or Sensor 2
Degraded)) or Drift Alert
Uncertain
Bad
Primary Value 1/Uncertain
Hot Backup Active and (Sensor 1 out of operating range or
Sensor 1 Degraded) and (Sensor 2 Open or short or Beyond
operating range)
Bad
Good
Primary Value 2/Good
Sensor 1 open or short or Beyond operating range
Bad
Uncertain
Primary Value 2/Uncertain
Sensor 1 open or short or Beyond operating range and
(Sensor 2 out of operating range or Sensor 2 Degraded)
Bad
Bad
None (Last good value)/Bad
Hot Backup Active and (Sensor 1 open or short or beyond
operating range) and (Sensor 2 open or short or beyond
operating range)
Summary of Contents for Rosemount
Page 1: ...Reference Manual 00809 0100 4021 Rev GC April 2014 Rosemount 3144P Temperature Transmitter ...
Page 2: ......
Page 4: ...iv Reference Manual 00809 0100 4021 Rev GC Title Page April 2014 ...
Page 10: ...x Reference Manual 00809 0100 4021 Rev GC Table of Contents April 2014 Table of Contents ...
Page 38: ...28 Reference Manual 00809 0100 4021 Rev GC Section 2 Installation April 2014 Installation ...
Page 188: ...178 Reference Manual 00809 0100 4021 Rev GC Section 5 Maintenance April 2014 Maintenance ...
Page 250: ...Index 244 Reference Manual 00809 0100 4021 Rev GC Index April 2014 Index ...
Page 251: ......